Installation examples
2-B-C: 1 heating zone + plate heat exchanger
37
2-B-C: 1 heating zone + plate heat exchanger
Description
•
R600 with plate heat exchanger
•
Weather compensated control (E8 or
LOGON B)
•
1 mixed heating zone
Tips
•
Complete accessory kits with plate
heat exchanger are available for
∆
T=10-20K (see chapter
„Accessories“).
•
The primary circuit should be de-
signed for
∆
T=20K, this guarantees a
high boiler efficiency.
•
When the secundary circuit is de-
signed for a
∆
T smaller than 20K, the
flow temperature of the plate heat
exchanger will be lower than the flow
temperature of the boiler. This should
be taken in consideration during the
design stage.
•
The plate heat exchanger should be
positioned close to the boiler, to avoid
a negative influance on the tempera-
ture control quality.
•
In case of a boiler room installed on
the roof, the boiler may never be hy-
draulically connected at the highest
point of the installation.