Installation examples
4-5-A-C-E: 2 heating zones and sanitary hot water + cascade via low loss header
42
4-5-A-C-E: 2 heating zones and sanitary hot water + cascade via low loss header
Description
•
2x R600 with low loss header
•
Cascade c weather compen-
sation (KKM8)
•
2 mixed heating zones
•
Sanitary hot water
Tips
•
Low loss duo headers are available
for
∆
T=15-20K (see chapter
„Accessories“).
•
The primary circuit should be de-
signed for
∆
T=20K, this guarantees a
high boiler efficiency.
•
When the secundary circuit is de-
signed for a
∆
T smaller than 20K, the
flow temperature in the header will be
lower than the flow temperature of the
boiler. This should be taken in consid-
eration during the design stage.
•
The header should be positioned
close to the boiler, to avoid a negative
influance on the temperature control
quality.
•
In case of a boiler room installed on
the roof, the boiler may never be hy-
draulically connected at the highest
point of the installation.