SAFETY  PRECAUTION

This manual uses the following symbols to ensure safe operation of this product.

WARNING

CAUTION

Warnings are indicated when mishandling this product might result in death or serious injury 

Cautions are indicated when mishandling this product might result in minor injury to the user, 

to user.

or only physical damage to the timer.

Note this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has 

    been correctly wired before turning the power ON.

Before wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause 

    electric shock.

Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.

Do not disassemble the product. Doing so might cause electric shock or faulty operation.

Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage, 

    shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation.

Firmly tighten the wires to the terminal. Insufficient tightening of the wires to the terminal might cause fire.

WARNING

CAUTION

ANLY ELECTRONICS CO., LTD.

http://www.anly.com.tw

When using this product in applications 
that require particular safety or when 
using this product in important facilities, 
please pay attention to the safety of the 
overall system and equipment. Install fail-
safe mechanisms, perform redundancy 
checks and periodic inspections and 
adopt other appropriate safety measures 
when it is necessary. This product is rated 
at Class 

Ⅱ     

.

RESTRICTIONS ON USE

 V

 S

L1
L2
L3

L1
L2
L3

 V

 S

L1
L2
L3

 V

 S

L1
L2
L3

 V

 S

NO INPUT

UNBALANCE VOLTAGE

REVERSE PHASE

PHASE LOSS

UNDER VOLTAGE

OVER VOLTAGE

 V

 S

L1
L2
L3

 V

 S

L1
L2
L3

 V

 S

L1
L2
L3

 V

 S

L1
L2
L3

 V

 S

L1
L2
L3

 V

 S

L1
L2
L3

 V

 S

 V

 S

 V

 S

L1
L2
L3

L1
L2
L3

L1
L2
L3

1. 3-phase voltages display

2. Fault indications

Phase-to-phase voltages
are displayed in sequence.

Set the desired value for over voltage.
The display will show existing 3-phase 
voltages after 10 seconds.

Set the desired value for under voltage.
The display will show existing 3-phase 
voltages after 10 seconds.

Set the tripping delay for under voltage.
The display will show existing 3-phase 
voltages after 10 seconds.

Set the tripping delay for over voltage.
The display will show existing 3-phase 
voltages after 10 seconds.

3. Over voltage tripping delay setting

1. Over voltage setting

4. Under voltage tripping delay setting

2. Under voltage setting

Operating  voltage

Life

Mechanical : 5,000,000 times  /  Electrical : 100,000 times

voltage  range

Allowable  operating

85 ~ 110% of  rated  operating  voltage

Rated  frequency

50 / 60 Hz

Display error

±

1%(at 550V)

Contact  rating

250VAC 5A (Resistive  load)

Power  consumption

Approx.  3.3VA

Ambient  temperature

-10 ~ +50 ºC (without condensation & freezing) 

Ambient  humidity

MAX  85% RH (without condensation)

Altitude

MAX 2000m

Weight

Approx.  130g

AC/DC : 100 - 240V, DC : 8 - 60V(for EP4-11060- only)

REV.

ON

OFF

ON

OFF

ON

OFF

ON

OFF

UNBAL.

AUTO

5S/1S

Auto reset

Auto reset delay 5 sec

Auto reset delay 1 sec

Manual reset

Phase reversal  protection ON

Unbalance protection ON

Unbalance protection OFF

Phase reversal  protection OFF

 V

 S

L1
L2
L3

L1
L2
L3

 V

 S

L1
L2
L3

L1
L2
L3

 V

 S

 V

 S

OVER VOLTAGE
SETTING VALUE

UNDER VOLTAGE
SETTING VALUE

OVER VOLTAGE DELAY

UNDER VOLTAGE DELAY

5. DIP switches setting

6. Setting display

Pressing "TEST" will cycle-through all 
settings in sequence.
3-phase voltages are displayed after 
10-second of idle.

Unbal.

Auto

Off

5S
1S

Rev.

Over

Volt

Under

Over

Volt

Under

Under

Over

Over

Time

Time

Under

EP4-1

L2

L2

L3

L3

L1

L1

S

V

Test

Over

Unbal.

Auto

Off

5S
1S

Rev.

Voltage

Time

Under

Over

Under

Reset

Voltage indicatior

Over voltage 
tripping delay

Time indicatior 
in second

Under voltage 
tripping delay

Function settings

Manual reset

Display

Under voltage setting

Phase sequence

Setting values display

Over voltage setting

NAMES AND FUNCTIONS OF FACEPLATE

SPECIFICATIONS

SETTING PROCEDURE

DISPLAY

DIMENSIONS

90.6

45

45

68.1

90.6

94.6

56.6

18