EN
32
Output (load) On/Off
When the charge controller is supplied with voltage, press the load switch (6) to connect and
disconnect the voltage to the output/load.
FIG. 7
Battery type setting
1.
Switch to settings mode by pressing the button for 5 seconds until the battery status light starts flashing.
2. Select the required type of battery by pressing the button.
3. The set type of battery is saved automatically if the button is not pressed for 5 seconds, and the
status light stops flashing.
Battery type indicator
Status light 1
Status light 2
Status light 3
Battery type
Off
On
On
Sealed (standard setting)
Off
Off
On
Gel (GEL)
Off
Off
Off
Wet cell (FLd)
BATTERY VOLTAGE LIMITS AND CHARGING TIMES
The voltages limits below apply for 12 V system at 25°C. Multiply by 2 for 24 V system.
Battery type
Sealed (SEL)
Gel (GEL)
Wet cell (FLd)
Overvoltage, disconnection limit
16.0 V
16.0 V
16.0 V
Charging voltage, charging stopped
15.0 V
15.0 V
15.0 V
Overvoltage, reconnection limit
15.0 V
15.0 V
15.0 V
Charging voltage, equalisation charging
14.6 V
—
14.8 V
Charging voltage, peak charging
14.4 V
14.2 V
14.6 V
Charging voltage, float charging
13.8 V
13.8 V
13.8 V
Charging voltage, limit for return to peak charging 13.2 V
13.2 V
13.2 V
Undervoltage, reconnection limit
12.6 V
12.6 V
12.6 V
Undervoltage, warning stops
12.2 V
12.2 V
12.2 V
Undervoltage, warning trips
12.0 V
12.0 V
12.0 V
Undervoltage, disconnection limit
11.1 V
11.1 V
11.1 V
Undervoltage, over-discharge limit
10.6 V
10.6 V
10.6 V
Equalisation charging time
120 min
—
120 min
Peak charging time
120 min
120 min
120 min