ENGLISH
77
Ste Set / Legionella protection
1. Menu
settings
2.
Description of menu settings
Menu Description
Ste Set/Ste Inst.
Legionella protection
ON
Legionella protection ON
OFF
Legionella protection OFF (default: OFF)
ON Time
Time to start of electric heater
Time : 23:00 – 04:00 (default: 23:00 – 04:00)
OFF Temp
Temperature for stop of electric heater
Value :70°C (default: 70°C)
When the function is on,
this symbol is shown in the display.
When the function and
electric heater
are on,
this symbol flashes.
If electric heater is
ON
and legionella protection is
ON
when the temperature in the tank is less
than 70°C for 7 days, the electric heater starts at 23:00 on the 7th day, heats up the water to 70°C,
and switches off when it reaches this temperature. If the water in the tank is still less than 70°C at
4:00 on the 8th day, the electric heater switches off. If the
tank overheating protection
is set to
less than 70°C, the electric heater only heats up the water to
the set tank overheating protection
temperature.
Summary of Contents for 417-031
Page 88: ...SVENSKA 8 Montering av kontrollpanel 1 Montering av bakstycke...
Page 89: ...SVENSKA 9 2 Montering av panel...
Page 94: ...SVENSKA 14 HT Set verhetningsskydd 1 Inst llningar...
Page 100: ...SVENSKA 20 2 Hur man s tter gr sv rdena f r automatiskt l ge...
Page 101: ...SVENSKA 21 3 Hur man ndrar viktiga v rden 4 Anv ndning av knappen...
Page 107: ...NORSK 27 Montering av kontrollpanel 1 Montering av bakstykke...
Page 108: ...NORSK 28 2 Montering av panel...
Page 114: ...NORSK 34 HT Set overopphetingsvern 1 Innstillinger...
Page 120: ...NORSK 40 2 Slik settes grenseverdier for automatisk modus...
Page 121: ...NORSK 41 3 Slik endres viktige verdier 4 Bruk av knappen...
Page 127: ...POLSKI 47 Monta panelu sterowania 1 Monta tylnej cz ci...
Page 128: ...POLSKI 48 2 Monta panelu...
Page 134: ...POLSKI 54 HT Set zabezpieczenie przed przegrzaniem 1 Ustawienia...
Page 140: ...POLSKI 60 2 Spos b ustawiania warto ci granicznych dla trybu automatycznego...
Page 141: ...POLSKI 61 3 Spos b zmiany istotnych warto ci 4 Spos b u ycia przycisku...
Page 147: ...ENGLISH 67 MOUNTING OF CONTROL PANEL 1 Mounting of back...
Page 148: ...ENGLISH 68 2 Mounting of panel...
Page 154: ...ENGLISH 74 HT Set overheating protection 1 Settings...
Page 160: ...ENGLISH 80 2 How to set limiting values for automatic mode...
Page 161: ...ENGLISH 81 3 How to change important values 4 Using the button...