Antaira Technologies - Industrial Ethernet Switches
LMP-1204G-SFP Hardware Manual V1.3
9
Figure 2.8 - Wiring the Fault Alarm Contact
Note:
Only use copper conductors, 60/75
°
C, tighten to 5lbs.
•
The wire gauge for the terminal block should range between 18~20 AWG.
2.9 Wiring the Fault Alarm Contact
The fault alarm contact is in the middle of the terminal block connector as the picture shows below
in
Figure 2.8
. By inserting the wires, it will detect the fault status including power failure or port link
failure (managed industrial switch only) and forma normally open circuit. An application example
for the fault alarm contact is shown below in
Figure 2.8
.
Caution:
The wire gauge for the terminal block should range between 12 ~ 24AWG
If only using one power source, jumper Pin 1 to Pin 5 and Pin 2 to Pin 6 to
eliminate power fault alarm.
2.10 Grounding Note
Grounding and wire routing help limit the effects of noise due to electromagnetic interference (EMI).
Run the ground connection from the ground screw to the grounding surface prior to connecting
devices. The grounding screw symbol is shown blow in Figure 2.15.
Figure 2.15 - Grounding screw
Caution:
Using a shielded cable achieves better electromagnetic compatibility.