a )  For other series module, fix the module with the long side (Drawing 4-a) or short side (Drawin 4-b)  

 

   

  according to the bracket designation and mechanical load requirement.

L

e

e

a

L

e

e

a

L/2

e

e

a

w

L/8 ≤ e ≤ L/4, a ≥ 6 cm 2400 Pa 

Drawing 4-a fixing on the long side

for the other module series

L/8 ≤ e ≤ L/4, a ≥ 6 cm 5400 Pa 

Drawing 4-a fixing on the long side

for the other module series

w/8 ≤ e ≤ W/4, a ≥ 6 cm 2400 Pa 

Drawing 4-b fixing on the Short side

for the other module series

Summary of Contents for PV MODULES Series

Page 1: ...LIVING BY THE SUN INSTALLATION MAINTENANCE MANUAL FOR PV MODULES ANTARIS SOLAR...

Page 2: ...ng an opaque cloth or other materials shall be used to cover the frontage of the Modules for the reason that monolithic module may produce potentially fatal current or voltage in the direct sunlight 5...

Page 3: ...he short circuit current and open circuit voltage value marked on this module shall be multiplied by a factor safety factor of 1 25 5 The Modules shall be installed in the position of the sun exposure...

Page 4: ...g 2 B Fixture fixing Fix the module safely and effectively on the brackets with special installation tools a For a Series 156 72 modules Six clamps must be used Drawing 3 L e e L 2 a L L 2 e e w Stand...

Page 5: ...acket designation and mechanical load requirement L e e a L e e a L 2 e e a w L 8 e L 4 a 6 cm 2400 Pa Drawing 4 a fixing on the long side for the other module series L 8 e L 4 a 6 cm 5400 Pa Drawing...

Page 6: ...xing on the long side for the other module series Drawing 5 fixing with sideway for A series modules Drawing 5 fixing with sideway for A series modules C Inserting System Fx the module with U type gro...

Page 7: ...on holes simultaneously is recommended according to the Security Considerations In the correct installation method the Modules could maximumly bear snow pressure of 5400 Pa or wind pressure of 2400 Pa...

Page 8: ...and assorted connector could be used to extend the connecting wire The cross sectional area shall be no less than 4 mm2 and the connection system shall reach IP65 protection rating 14 The minimum sepa...

Page 9: ...ruction Periodic cleaning is necessary for solar module which could reduce the loss due to dust and is recommended by ANTARIS SOLAR The cleaning processes should be accomplished by the professionals w...

Page 10: ...tallation handling use or maintenance 2 ANTARIS SOLAR assumes no responsibility for any infringement of intellectual property right including without limitation patent copyright and trademark or other...

Page 11: ...ANTARIS SOLAR GmbH Co KG Head office 63735 Aschaffenburg Germany Phone 49 0 6095 950 441 Fax 49 0 6095 950 544 Email info antaris solar com Internet www antaris solar com Member of...

Reviews: