ASP-8/10/12/15KTLC
21
Power grid voltage: 310 V - 480 VAC, Power grid frequency:
45-55 Hz / 55-65 Hz
Cable:
AC and DC wiring should conform to local safety standards. Wire diameter should
guarantee basic flow capacity.
Table 4-1 Cable specification
Cable
ASP-8/10/12/15KTLC
PV Array+
Wire Diameter
5-6mm²
PV Array -
5-6mm²
AC cable
6-10mm²
RS485
Shielded signal cable
Circuit Breakers
In order to guarantee its safe operation and installation, the inverter needs to be
configured with manual circuit breakers. The breaker needs to conform to local
safety standards, and has basic protections against over current and over voltage.
AC breaker’s voltage and current need to be higher than 450V, 32A, and DC
breaker higher than 1000V, 25A.