ASP-8/10/12/15KTLC
36
4.Check whether the machine ventilation,
articulated installation, and air duct are ok
5. Check whether the output power is higher than
the rated value
Ground Fault
1. Disconnect the AC circuit breaker
2. Disconnect the DC circuit breaker
3. Check whether resistance of each group of PV
arrays to the ground is > 2 M
Ω
Table 7-1 Type of faults
If the fault cannot be solved or your problem is not mentioned in the above table,
please contact us.
8. Appendix
8.1 Technical Parameters
Technical Parameters
ASP-8
KTLC
ASP-10
KTLC
ASP-12
KTLC
ASP-15
KTLC
Input Data
Max. DC power
10400W
13000W
15600W
18000W
Max. DC voltage
1000V
MPPT voltage range
250V
~
950V
Max. DC current
11/11A
22/11A
Recommended
PV
array working voltage
650V
MPP tracker number
2
Max. inputs per MPP
tracker
1
1
2/1
2/1