24
TC5-2V2SA.rev.05
•
When
room temperature < Set Point
, stage 1 fans run at minimum
speed according to the minimum ventilation cycle.
•
At Set Point
: stage 1 fans stop operating according to the minimum
ventilation cycle and increase in speed as the room temperature rises.
•
At Set Point + Bandwidth 1
: stage 1 fans reach full speed.
•
At Set Point + Bandwidth 1 + Stage 2 Offset
: stage 2 fans start
running.
If room temperature rises:
The TC5-2V2SA controls two stages of variable-speed fans (Stage 1 - 2),
two optional stages of constant-speed fans (Stage 3 - 4).
VENTILATION SETTINGS
C
OOLING OPERATION
Room
Temp.
Temperature
Set Point
STAGE 1
STAGE 2
STAGE 3
STAGE 4
Bandwidth
Stage 1
Minimum
Ventilation
Cycle
Bandwidth
Stage 2
Offset
Stage 2
Differential
Stage 3
Differential
Stage 4