41
TC5-2V2SA.rev.05
TC5-2V2SA
ON
OFF
TIME ON
TIME OFF
If the humidity compensation is activated, the mist units are turned off
when the humidity reaches a user-defined maximum humidity level.
The mist units operate according to a timer cycle. Time on is the running
time of the mist units and time off is the off time of the mist units.
M
IST COOLING
NUMBER OF HEATING STAGES
MIST STAGE
0
4
1
3
T
he last cooling stage can be configured as a mist stage. To activate mist
cooling, set internal switch #9 to ON. The number of heating stages determines
which stage this is.
When two heating stages are used, a mist stage cannot be configured.
The following diagram sums up the operation of the mist units.
Mist units turn off
Room
Temperature
Set Point
Mist
Mist Offset
OFF
Mist units turn on
in timer mode
Diff.