7
!
!
Ethernet and also because of an excessive number of files, their sizes, and type and manufacturer of the USB memory
(pendrive) used
6. ENCLOSURE DIMENSIONS AND INSTALLATION DATA
Enclosure type
panel, Incabox XT L57
Material
self-extinguishing NORYL 94V-0,
polycarbonate
Enclosure dimensions
96 x 96 x 79 mm
Panel window
92 x 89 mm
Fixing methods
grips on the side of the enclosure
Conductor cross-
sections (
separable
connectors)
2.5 mm
2
(supply and alarm outputs),
1.5 mm
2
(others)
NOTE:
The antenna or the antenna cable must be fixed with screws manually without using tools so as not to damage the
socket.
7. DESCRIPTION OF TERMINAL STRIPS AND ELECTRICAL CONNECTIONS
Location, numbering, and description of the connections on the back panel and method of connecting probes
and electrical signals:
Terminal clamps
(connections)
Description
ANTENNA
SMA socket to connect an antenna for the 868 MHz band
1-2-3
IN1-IN2-IN3 - input of the wired temperature probe AR182 or AR183
41÷44
serial interface RS485, MODBUS-RTU transmission protocol, MASTER (connecting Apar
devices) or SLAVE (connecting to a computer, a PLC, etc.), chapters 17 and 18
45÷52
relay outputs P1, P2, P3, and P4 or SSR1, SSR2, SSR3, and SSR4
53-54
power supply input 230 VAC or 24 VAC/DC
ETHERNET
serial Ethernet interface (type 100base-T, RJ45 socket, TCP/IP protocols)
USB
serial USB interface (programmable operation mode: device or host, chapter 12.8,
do not use two USB sockets at the same time
)
NOTE:
A USB connection is also available on the
front panel.
DO NOT USE SIMULTANEOULY WITH THE
BACK CONNECTION!
Summary of Contents for AR407