Operation
Document No. D106-009
Page 53 of 76
Revision 1.15
Parameter
Datatype Description
RoutingInhibit
BOOL
This bit inhibits the module routing capabilities.
When set, no Modbus messages will be routed. This may be
required in applications running a redundant Modbus network
where one of the Modbus Routers is to run in a hot-standby mode.
Table 4.2 - RSLogix 5000 output assembly parameters
4.3.
UNSCHEDULED MESSAGING
When the Modbus Router is configured in Unscheduled Mode, it will process Modbus
message requests sent from Logix via a message instruction.
NOTE:
The user will need to build some of the Modbus request data of the
unscheduled message.
NOTE:
When in unscheduled mode the Controller Type selection in the General
configuration will not be applicable. The Modbus Router will only support a
Logix Controller type in unscheduled mode.
To simplify the configuration of the required message a number of UDTs have been
preconfigured, and are available on the Aparian ModbusRouter webpage (see the further
information section).
The message instruction should be setup as follows:
Figure 4.3. - Message Instruction