AH-New
condensing air handling unit
APEN GROUP SPA reserves the right to make changes deemed to be required to its products or documentation
12
code HG0310.05GB ed.A-2010
AH
13
code HG0310.05GB ed.A-2010
AH
Model
AH160 - R
AH210 - R
AH320 - R
AH420 - R
Type of equipment
B23P - C11 - C13 - C33 - C43 - C53 - C63
EC approval
PIN
0476DL4298
NOx class [EN17082:2019]
5
Type of fuel
Gaseous
Heater Performance
min
max
min
max
min
max
min
max
Burner heat output (Hi)
kW
16.40
152.00
21.00
180.00
21.00
270.00
21.00
360.00
Useful heat output [P
min
,
P
rated
]*
kW
17.77
148.66
22.77
176.76
22.77
265.14
22.77
353.52
Hi Efficiency (N.C.V.) [
ƞ
pl
,
ƞ
nom
]*
%
108.35
97.80
108.40
98.20
108.40
98.20
108.40
98.20
Hs efficiency (G.C.V.) [
ƞ
pl
,
ƞ
nom
]*
%
97.62
88.12
97.68
88.48
97.68
88.48
97.68
88.48
NOTES:
*
Symbol in compliance with Reg.EU/2281/2016.
B - “R” Version Modules
Single-module air handling units have a useful heat efficiency, at
a load equal to 100% of the nominal useful heat output, greater
than or equal to 93+2LogPn.
For multiple-module AH air handling units, Apen Group has an
"R" version, intended only for the Italian market, which complies
with the requirement mentioned above, i.e. 93+2LogPn.