6.6.
Country Table - Gas Category
Country
Category
Gas
Pressure
Gas
Pressure
AT, CH
II2H3B/P
G20
20 mbar
G30/G31
50 mbar
BE <70kW
I2E(S)B, I3P
G20/G25
20/25 mbar
G31
37 mbar
BE >70kW
I2E(R)B, I3P
G20/G25
20/25 mbar
G31
37 mbar
DE
II2ELL3B/P
G20/G25
20 mbar
G30/G31
50 mbar
DK, FI, GR, SE,
NO, IT, CZ, EE, LT,
SI, AL, MK, BG,
HR, TR
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
RO
II2L3B/P
G25
20 mbar
G30/G31
30 mbar
ES, GB, IE, PT, SK
II2H3P
G20
20 mbar
G31
37 mbar
FR
II2Esi3P
G20/G25
20/25 mbar
G31
37 mbar
LU
II2E3P
G20/G25
20 mbar
G31
37/50 mbar
NL
II2EK3B/P
G20/G25.3
20/25 mbar G30/G31
30 mbar
HU
II2HS3B/P
G20/G25.1
25 mbar
G30/G31
30 mbar
CY, MT
I3B/P
G30/G31
30 mbar
LV
I2H
G20
20 mbar
IS
I3P
G31
37 mbar
PL
II2ELwLs-
3B/P
G20/G27/G2.350 20/13 mbar G30/G31
37 mbar
RU
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
The following information is clearly printed on the packaging of every AHU: country of destination, gas category and equipment code.
The code allows finding out the factory settings.
NOTE: In compliance with standards EN17082, EN 437 and ISO3166, GB refers to the United Kingdom.
Codes with no extension:
•
AH105IT
if there is no extension, it means that the equipment has been tested and set to run with natural gas
[G20].
Codes with extension:
The fourth letter indicates the type of gas the equipment has been set up for:
•
AH105FR xxx0
0 indicates that the equipment has been tested and set up for natural gas [G20];
•
AH105MT-xxx1
1 indicates that the equipment has been tested and set up for LPG [G31];
•
AH105NL-xxx2
2 indicates that the equipment has been tested and set up for 'L' [G25] or ‘K’ [G25.3] natural gas;
•
AH105HU xxx3
3 indicates that the equipment has been tested and set up for natural gas [G25.1];
•
AH105PL xxx4
4 indicates that the equipment has been tested and set up for gas [G2.350].
Another adhesive label, located near the fuel connection of the equipment, specifically indicates the type of gas and the supply
pressure for which the equipment has been set up and tested.
NOTE: The unit is supplied already set for natural gas [G20] and equipped with the kit for conversion to LPG.
The kit for conversion to LPG is not supplied in countries where conversion is prohibited.
NOTE: Conversion is strictly prohibited in some countries, such as Belgium, which do not allow the double gas category.