wiring of each UPS.
5) Connect the output wires of each UPS to an output breaker panel.
6) Disconnect the Jumper on JP1 and JP2 of the terminal block first, and connect each
output breaker to a main output breaker and then to the loads.
7) Each UPS need an independent battery pack.
8) Please refer to the wiring diagram in the following diagram.
9) The distance between the UPSs in parallel and the breaker panel is required to beless
than 20 meters.The difference between the wires of input and output of the UPSs is
required to be less than 20%.
10) Do not switch on the output breakerof each UPS, switchon the input breaker ofthe each
UPS, the UPS should work in bypass with output, observe their displayto check if there
are any warning or fault information,measure the outputvoltage of each UPS separately
tocheck if the voltage difference between them is less than 1V. If the difference is more
than 1V, check the wiring.
11) Press the button of one UPS, each UPS would start to turn on, all the UPSs would
transfer tothe INV mode together. Measure the outputvoltage of each UPS separately