Figure 7. Crimping Wiretaps onto Wires

Figure 8. Wiretap Connec� ons

Wiring the Connections

Before connec� ng the wires from the interconnect base, iden� fy the (+) line (hot) 

120VAC wire and the neutral wire. Usually the (+) line (hot) 120VAC wire will be black 

and the neutral wire white. Use a voltmeter or voltage sensor to verify that the proper 

wires are selected. You may need to reconnect power to the electrical circuit powering 

the interconnected hardwired smoke detectors in order to do this (Figure 8).

WARNING: Remember to disconnect or shut off  electrical power to the interconnected 

hardwired smoke detector if it was powered on in the previous step to iden� fy  the  

120VAC wires.

Use an electrician’s linesman plier or equivalent tool (See Figure 8) and using the installed 

wiretaps on the device, crimp the wiretap with the black wire onto the  120VAC line 

(hot) wire.

ATTENTION : Ne pas oublier de déconnecter ou couper le courant électrique pour le 

détecteur de fumée câblé s’il avait été alimenté auparavant pour iden�  er les  ls 120 AC.

U� liser une pince d’électricien ou un ou� l équivalent (voir image 8) et en u� lisant les 

connecteurs installés sur l’appareil, ser� r le connecteur avec le  l noir sur la ligne 120VAC 

(posi� f). 

 

NOTE: Wiretaps must be used on a sec� on of stranded wire. This is typically located 

between the connector to the smoke detector and the wire nut.

The wiretap with the yellow wire should be a� ached to the wire lead connected to the 

interconnect wire of the smoke detector. This wire is typically yellow or orange.

Once all  (3) three wiretaps have been installed (Figure 8), rea� ach the electrical wire 

pigtail to the back of the smoke detector unit and mount the smoke alarm on the 

moun� ng base (Refer to Figure 3).

Installing the Back-Up Battery

Figure 9. Installing Back-up Ba� ery

WARNING: Ensure that the interconnect base has been wired correctly. Damage to 

the interconnect base may occur if the  120 VAC line (hot) wire neutral wire are reversed. 

The unit may fail to func� on properly if incorrectly wired.

Turn on or reconnect power to the primary electrical circuit that powers the 

interconnected hardwired smoke alarm system. The device should now power on.

Use a  at bladed tool, slide out the ba� ery tray that holds the backup ba� ery. Insert 

a CR2032A ba� ery (included) into the ba� ery slot. Slide the ba� ery tray back into the 

device (Figure 9).

ATTENTION : S’assurer que le détecteur de fumée a été branché correctement. Le capteur 

du détecteur de fumée pourrait être endommagé si le  l de la ligne 120AC (posi� f) et 

le  l neutre sont inversés. L’appareil pourrait ne pas fonc� onner correctement s’il était 

mal branché. Etablir ou rétablir le courant du circuit électrique principal qui alimente 

le système câblé de détec� on de fumée. L’appareil devrait à présent s’allumer. U� lisant 

un ou� l à lame plate, coulisser le � roir de la pile de sécurité. Insérer une pile CR2032A 

(incluse) dans l’emplacement. Coulisser à nouveau le � roir pour le refermer (image 9). 

 

NOTE: Orient the (+) ba� ery terminal up so that it is visible when facing the unit.

Programming the Wireless Smoke Alarm Interconnect Base

Follow the instruc� ons on how to program a sensor into a compa� ble control panel. See 

the control panel’s Installa� on & Programming Guide for more informa� on on how to 

learn a sensor into the control panel.

The device should learn in as a sensor device. Use a small paper clip or other sharp 

object and carefully insert into the learn/test bu� on hole. This will send out an alarm 

transmission ID so the the sensor can be learned into a compa� ble control panel or can 

be used to test that the transmi� er is working properly.

Replacing the Battery

If the compa� ble control panel shows that this sensor has a low ba� ery, the backup 

ba� ery may need to be replaced.

Use a  at headed screw driver or other tool to slide the ba� ery tray out of the device. 

Remove the ba� ery from the tray and replace with a new CR2032A ba� ery. Slide the 

ba� ery tray back into the unit, making sure that the tray is fully inserted into the unit.

 

NOTE: Use Panasonic CR2032A ba� eries or equivalent. Use of another ba� ery may 

damage or nega� vely aff ect the opera� on of the device.

End-of-Life

The Wireless Smoke Alarm Interconnect Base does not have an End-of-Life (EOL), however 

the smoke alarm(s) that this device monitors may have an EOL condi� on. Follow the 

owner's manual for the smoke alarm regarding instruc� ons on proper smoke alarm EOL 

condi� ons.

LED Status

Status

LEDs

Radio Signaling

PowerOn

Sequential green, orange, red fl ashes

N/A

Normal

Green LED fl ash every 48s

N/A

Alarm

Red fl ash every 1s

Alarm

Loss of AC Power 
Fault

Orange fl ash every 20s

Tamper

Low Battery Fault

Orange fl ash every 4s

Low Battery

Learn Button

Sequential green, orange, red fl ashes

Alarm

Testing the Smoke Alarm System

Figure 10. Loca� on of LEDs and Learn/Test Bu� on Hole

The device should be tested in accordance with NFPA 72 guidelines. The following

instruc� ons are intended to provide a general guideline on how to test the smoke alarm 

system, wireless smoke alarm interconnect base and communica� ons to an alarm panel.

Follow the smoke alarm instruc� on manual on tes� ng the smoke alarm and any 

interconnected units. There usually is a test bu� on on the smoke alarm that can be 

pressed to ini� ate a test mode. This should cause the sounder to alarm and also any 

smoke alarms that are interconnected to also alarm.

The interconnect base should send out a transmission to a compa� ble alarm panel. 

If this transmission is not received,  rst check if the Smoke alarm is properly programmed 

into a compa� ble alarm panel. Please follow the alarm panel instruc� ons on learning in 

a sensor.

Also, check that the interconnect wire on the smoke alarm is properly connected to the 

Wireless Smoke Alarm Interconnect Base. The LEDs on the interconnect base should 

 ash red indica� ng that it has received the alarm signal from the smoke alarm . 

Testing the Wireless Smoke Alarm Interconnect Base Radio Trans-

mission Only

The Wireless Interconnect Base incorporates a small test bu� on. This test bu� on can be 

ac� vated by inser� ng a straightened paper clip or sharp object into the Learn/Test hole. 

The Smoke Detector Sensor will then send an alarm signal transmission to a compa� ble 

alarm panel. This can be used to test that the Wireless Smoke Alarm Interconnect Base 

will send a proper transmission to an alarm panel. This DOES NOT test if the wiring 

between the smoke alarm and the interconnect base is correct.

Troubleshooting Installation Chart

When tes� ng the Wireless Smoke Alarm Interconnect Base sensor, check for these 

common issues.

Condition

Smoke Alarm

Result

Resolution

Wireless Smoke Alarm 
Interconnect Base LED

Alarm Panel

Smoke detector is in 
alarm mode

LED on interconnect base 
do not work properly

Alarm panel does not 
receive alarm signals

Check to make sure 
interconnect wire from 
the smoke alarm is 
properly connected to the 
interconnect base

Smoke detector is in 
alarm mode

LED on interconnect base 
sensor works properly

Alarm panel does not 
receive alarm signals

Check to make sure 
the interconnect base 
is properly learned or 
programmed into a 
compatible alarm panel

EXISTING 
POWER
 PIGTAIL

WIRETAPS (3)
CRIMPED 
TO PRIMARY
CIRCUIT WIRES

WIRING CODE:
• BLACK TO BLACK
 (120 VAC)
• WHITE TO WHITE (NEUTRAL)
• YELLOW TO YELLOW OR
  ORANGE (INTERCONNECT)

PRIMARY POWER
WIRING

WHT/WHT (NEUTRAL)

BLK/BLK (120VAC)

YEL/YEL OR
YEL/ORANGE

+

CR2032

3V

MOVE TO

FRESH AIR

SMOKE

+

CR2032

3V

STEP 1
PULL OUT
BATTERY TRAY
WITH FLATHEAD
SCREWDRIVER

STEP 2
INSERT 
BATTERY 

+ POLARITY

FACING UP

WIRELESS SMOKE ALARM
INTERCONNECT BASE

SMOKE ALARM 

LEDS ON WIRELESS SMOKE
ALARM INTERCONNECT BASE

LEARN/TEST BUTTON
HOLE

1. PLACE WIRE 
INTO
WIRETAP.

2. HINGE WIRETAP
UP AND OVER 
WIRE STRAND

3. CRIMP
WIRETAP WITH
PLIERS

WIRING CODE:
•BLACK TO BLACK (120 VAC)
•WHITE TO WHITE (NEUTRAL) 
•YELLOW TO YELLOW OR
  ORANGE (INTERCONNECT)