• Refit the lid to the backbox, using the supplied screws. 

ELECTRICAL SCHEME FOR THE CONNECTION OF THE INPUT 

MODULE TO THE EXTERNAL DEVICE WHICH TRANSMITS 

THE INPUT SIGNAL TO THE MODULE

5

6

EXTERNAL

DEVICE

-     +

-     +

- +

• The 

10K

Ω

 R

        

resistor monitors whether the cable has been damaged

or the connection is no longer available.

• The 

5.6K

Ω

 R

    resistor comes in and out of circuit depending on the state

of the 3rd party device (alarm resistor).

• If you fail to install these resistors correctly the device will not operate  as 

intended. 

• Ensure the 3rd party device offers a voltage free relay switch. 

Note: install a properly fire-rated cable (according to national code of practice) 

between the third-party device and the input module.

EOL

AL

R

EOL

R

AL

R

EOL 

10 KΩ

R

EOL 

5.6 K Ω

RW1700-051APO

REACH Input Module

QUICK START GUIDE

Apollo Fire Detectors Ltd. 36 Brookside Road, Havant, Hampshire, United Kingdom, PO9 1JR
T: +44 (0)23 9244 2706 - E: techsales@apollo-fire.com - W: www.apollo-fire.co.uk

RW_QSG_MODULE_INPUT_REV_A.1