• Refit the lid to the backbox, using the supplied screws.
ELECTRICAL SCHEME FOR THE CONNECTION OF THE INPUT
MODULE TO THE EXTERNAL DEVICE WHICH TRANSMITS
THE INPUT SIGNAL TO THE MODULE
5
6
EXTERNAL
DEVICE
- +
- +
- +
• The
10K
Ω
R
resistor monitors whether the cable has been damaged
or the connection is no longer available.
• The
5.6K
Ω
R
resistor comes in and out of circuit depending on the state
of the 3rd party device (alarm resistor).
• If you fail to install these resistors correctly the device will not operate as
intended.
• Ensure the 3rd party device offers a voltage free relay switch.
Note: install a properly fire-rated cable (according to national code of practice)
between the third-party device and the input module.
EOL
AL
R
EOL
R
AL
R
EOL
10 KΩ
R
EOL
5.6 K Ω
RW1700-051APO
REACH Input Module
QUICK START GUIDE
Apollo Fire Detectors Ltd. 36 Brookside Road, Havant, Hampshire, United Kingdom, PO9 1JR
T: +44 (0)23 9244 2706 - E: techsales@apollo-fire.com - W: www.apollo-fire.co.uk
RW_QSG_MODULE_INPUT_REV_A.1