© Apollo Fire Detectors Limited 2015
10
Menu Level: (1.3)
Fault Status
Alarm Status
Battery Level
Signal Level
Manual Update
Ident
This menu shows the status of the two battery packs in a device. Battery
conditions are displayed as follows:
Displayed
Definition
Icon on LCD
Analogue value at panel
Pack 1 OK
Pack 1 battery voltage
healthy
Full battery icon
25 (detectors)
16 (sounders and MCPs)
Pack 1 Warning*
Pack 1, 30 day warning
Half battery icon
7
Pack 1 Low
Pack 1, 7 day warning
Empty battery icon
7
Pack 1 Missing
No battery pack fitted
X
0
Pack 2 OK
Pack 2 battery voltage
healthy
Full battery icon
25 (detectors)
16 (sounders and MCPs)
Pack 2 Warning*
Pack 2, 30 day warning
Half battery icon
7
Pack 2 Low
Pack 2, 7 day warning
Empty battery icon
7
Pack 2 Missing
No battery pack fitted
X
0
Recommended replacement batteries:
Alkaline Panasonic Powerline 1.5V AA (Size M, LR6)
Alkaline Varta Industrial 1.5V AA (4006, LR6)
Alkaline Panasonic Powerline 1.5V C (Size L, LR14) for sounders only
Alkaline Varta Industrial 1.5V C (4014, LR14) for sounders only
Note: When replacement batteries are required all batteries must be replaced together.
* Batteries need to be changed as soon as possible (recommendation 7 days)
Menu Level: (1.2)
Fault Status
Alarm Status *
Battery Level
Signal Level
Manual Update
Ident
This menu shows the alarm status of the device.
*
Input status
on Input Output Unit - Displays the status of the monitored
input(s). A switch input ‘closed’ condition is displayed as a logic ‘1’ For a
full range of analogue values please see Appendix A on page 14