SBX® Connectors
Assembly instruction for SBX®175 and SBX®350 Series
two pole battery connector with option for two auxiliary contacts
.
Contains one (1) housing and two (2) contacts.
1.
CONNECTOR RATINGS
SBX350 series: 350 AMPS with max cable size 300MCM
SBX175 series: 175 AMPS with max cable size 1/0
2.
RECOMMENDED CONTACT CRIMPING
RECOMMENDED CRIMP OUTLINE:
3.
REDUCING BUSHINGS:
recommended for fitting small cables to STD contacts assuring proper
crimp connection
CAUTION:
When using cable with jacket diameter less than 0.423 inches (11mm) on the SBX175 and less than 0.709 inches (18mm) on the SBX350
thin wall heat shrink insulation should be evenly applied across the cable and contact barrel junction to insure finger protection.
4.
CABLE STRIPPING DIMENSIONS
Connector Series
Bushing Size (AWG)
Catalog Number
SBX350
2/0 to 1/0
5918
SBX175
1/0 to 1
5687
1/0 to 2
5690
1/0 to 4
5693
1/0 to 6
5663
1/0 to 10
5648
Connector Series
Contact
Portable Hydraulic Tool
Pneumatic Tool
SBX350
2/0, 3/0, 4/0, 300MCM
1368
1387G1 & 1387G2
Heat Shrink Insulation Specifications
Connector
Nominal
Minimum
Maximum
Series
Tubing Size
Length
Wall Thickness
SBX350
.75 in (19mm)
2.0 in (51mm)
.030 in (.76mm)
SBX175
.50 in (12.7mm)
2.0 in (51mm)
.025 in (.63mm)
Connector
Strip “X” To
Series
Inches
m m
SBX350
1 3/8
35
SBX175
1 1/8
29
FOR INSTALLATION BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH
NATIONAL AND LOCAL ELECTRICAL CODES AND THE FOLLOWING INSTRUC-
TIONS. THE SUITABILITY OF THIS TYPE OF TERMINATION MUST BE EVALU-
ATED BY UNDERWRITERS’ LABORATORIES, INC. AND CANADIAN STANDARDS
ASSOCIATION FOR THE END USE APPLICATION.
Assemble contacts to the cables according to the equipment manufacturer’s as-
sembly instructions. The following instructions are supplied as a reference. Please
note: instructions are included with each crimp tool for terminating specific contacts.
[19.0] 0.75 MIN
[3.2] 0.12 MIN
[3.2] 0.12 MIN
X
7.
Cable ties are supplied to secure the auxiliary leads or cable to one of the main power cables.
Leave slack or loop in leads to Powerpole contacts when applying cable ties, figure1. Wraps to
be placed approximately 1 inch (25.4mm) apart as shown in figure 1.
8.
To remove auxiliaries, punch out pins from bottom with .06 inch (1.5mm) diameter steel rod or
pin driver. Also available: contact insertion-extraction tool kit (cat. #111038G2).
WARNING
UTMOST CAUTION SHOULD BE USED WHEN WORKING ON LIVE CONNECTOR CONTACTS
UL and CSA Reference - These connectors are recognized under the component program of Underwriters’
Laboratories, File E26226, as well as Canadian Standards Association, Report LR25154.
PATENTS AND TRADEMARKS
This product is covered by the following patents: U.S. 3,794,957; U.K. 1,443,819; France 73,44153; Italy
1,000442; Japan 885,802; South Africa 74/0939; Canada 990,821. Other U.S. and foreign patents pending.
“SBX, Powerpole and Anderson Power Products” are registered U.S. and foreign trademarks of Anderson
Power Products, 13 Pratts Junction Road, P.O. Box 579, Sterling, MA 01564 USA
1S1094 REV10 14162
ASM-SBX
HEADQUARTERS:
13 Pratts Junction Road, P.O. Box 579, Sterling, MA 01564 T:978-422-3600 F:978-422-3700
EUROPE:
Rathealy Road, Fermoy Co. Cork, Ireland T:353-(0)25-32277 F:353-(0)25-32296
ASIA/PACIFIC:
IDEAL Anderson Asia Pacific Ltd., Unit 922-928 Topsail Plaza, 11 On Sum Street, Shatin N.T., Hong Kong
T:852-2636-0836 F:852-2635-9036
CHINA:
IDEAL Anderson Technologies (Shenzhen) Ltd., Block A8 Tantou W. Ind. Par, Songgang Baoan District, Shenzhen, PR. China 51810
T: 86-755-2768-2118 F: 86-755-2768-2218
TAIWAN:
IDEAL Anderson Asia Pacific Ltd., Taiwan Branch, 4F.-2, No.116, Dadun 20th St., Situn District, Taichung City 407, Taiwan (R.O.C.)
T: 886-4-2310-6451 F:886-4-2310-6460
www.andersonpower.com
Figure 2
Loop Wire
[25]
1.0