SBX® Connectors

Assembly instruction for SBX®175 and SBX®350 Series

two pole battery connector with option for two auxiliary contacts

.

Contains one (1) housing and two (2) contacts.

1.

CONNECTOR RATINGS

SBX350 series: 350 AMPS with max cable size 300MCM
SBX175 series: 175 AMPS with max cable size 1/0

2.

RECOMMENDED CONTACT CRIMPING

RECOMMENDED CRIMP OUTLINE:

3.

REDUCING BUSHINGS: 

recommended for fitting small cables to STD contacts assuring proper

crimp connection

CAUTION:
When using cable with jacket diameter less than 0.423 inches (11mm) on the SBX175 and less than 0.709 inches (18mm) on the SBX350
thin wall heat shrink insulation should be evenly applied across the cable and contact barrel junction to insure finger protection.

4.

CABLE STRIPPING DIMENSIONS

Connector Series

Bushing Size (AWG)

Catalog Number

SBX350

2/0 to 1/0

5918

SBX175

1/0 to 1

5687

1/0 to 2

5690

1/0 to 4

5693

1/0 to 6

5663

1/0 to 10

5648

Connector Series

Contact

Portable Hydraulic Tool

Pneumatic Tool

SBX350

2/0, 3/0, 4/0, 300MCM

1368

1387G1 & 1387G2

Heat Shrink Insulation Specifications

Connector

Nominal

Minimum

Maximum

Series

Tubing Size

Length

Wall Thickness

SBX350

.75 in (19mm)

2.0 in (51mm)

.030 in (.76mm)

SBX175

.50  in (12.7mm)

2.0 in (51mm)

.025 in (.63mm)

Connector

  Strip “X” To

Series

Inches

m m

SBX350

1 3/8

35

SBX175

1 1/8

29

FOR INSTALLATION BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH
NATIONAL AND LOCAL ELECTRICAL CODES AND THE FOLLOWING INSTRUC-
TIONS.  THE SUITABILITY OF THIS TYPE OF TERMINATION MUST BE EVALU-
ATED BY UNDERWRITERS’ LABORATORIES, INC. AND CANADIAN STANDARDS
ASSOCIATION FOR THE END USE APPLICATION.

Assemble contacts to the cables according to the equipment manufacturer’s as-
sembly instructions.  The following instructions are supplied as a reference.  Please
note: instructions are included with each crimp tool for terminating specific contacts.

[19.0]  0.75 MIN

[3.2]  0.12 MIN

[3.2]  0.12 MIN

X

7.

Cable ties are supplied to secure the auxiliary leads or cable to one of the main power cables.
Leave slack or loop in leads to Powerpole contacts when applying cable ties, figure1.  Wraps to
be placed approximately 1 inch (25.4mm) apart as shown in figure 1.

8.

To remove auxiliaries, punch out pins from bottom with .06 inch (1.5mm) diameter steel rod or
pin driver.  Also available: contact insertion-extraction tool kit (cat. #111038G2).

WARNING
UTMOST CAUTION SHOULD BE USED WHEN WORKING ON LIVE CONNECTOR CONTACTS

UL and CSA Reference - These connectors are recognized under the component program of Underwriters’
Laboratories, File E26226, as well as Canadian Standards Association, Report LR25154.

PATENTS AND TRADEMARKS
This product is covered by the following patents: U.S. 3,794,957; U.K. 1,443,819; France 73,44153; Italy
1,000442; Japan 885,802; South Africa 74/0939; Canada 990,821.  Other U.S. and foreign patents pending.

“SBX, Powerpole and Anderson Power Products” are registered U.S. and foreign trademarks of Anderson
Power Products, 13 Pratts Junction Road, P.O. Box 579, Sterling, MA 01564 USA

 1S1094  REV10  14162

                     ASM-SBX

HEADQUARTERS:

 13 Pratts Junction Road, P.O. Box 579, Sterling, MA 01564  T:978-422-3600  F:978-422-3700

EUROPE: 

Rathealy Road, Fermoy Co. Cork, Ireland   T:353-(0)25-32277   F:353-(0)25-32296

ASIA/PACIFIC:

 IDEAL Anderson Asia Pacific Ltd., Unit 922-928 Topsail Plaza, 11 On Sum Street, Shatin N.T., Hong Kong

T:852-2636-0836   F:852-2635-9036

CHINA:

 IDEAL Anderson Technologies (Shenzhen) Ltd., Block A8 Tantou W. Ind. Par, Songgang Baoan District, Shenzhen, PR. China 51810

T: 86-755-2768-2118  F: 86-755-2768-2218

TAIWAN:

 IDEAL Anderson Asia Pacific Ltd., Taiwan Branch, 4F.-2, No.116, Dadun 20th St., Situn District, Taichung City 407, Taiwan (R.O.C.)

T: 886-4-2310-6451  F:886-4-2310-6460

www.andersonpower.com

Figure 2

Loop Wire

[25]