background image

303359 Rev. D 05/13 • Page 8 of 12

Service

!

 WARNING

Electrical power must be turned OFF before and during installation and maintenance. Failure to do so may result in serious or fatal 
injuries due to electrocution.

!

 WARNING

If any part of the receptacle appears to be missing, broken, or show signs of damage—discontinue use immediately! This condition 
could cause serious or fatal personal injury due to electrocution and/or equipment damage. Repair with the proper replacement part(s) 
before continuing service.

Disconnect Switch

Disconnect switches occasionally fail and need to be replaced. The disconnect switch used in this receptacle can be replaced with the 
same type and brand as factory installed and will not affect the UL Listing.

To Replace the Disconnect Switch:
1. 

Referring to Figure 2, remove the switch actuator stud (Item #11) by unscrewing it.

2. 

Remove the disconnect switch’s sliding and fixed plates (Item #14 & #20) by removing the two screws (Item #15).

3. 

Remove the clear plastic shield (Item #16) by loosening (but not removing) its holding screws.

4. 

Loosen the line and load side pressure screws (Item #8 & #9) and remove the line and load side wires from the disconnect switch (Item #6).

5. 

Remove the switch base plate (Item #12) by removing the switch base plate screws (Item #13).

6. 

Remove the disconnect switch from its base plate by taking out the switch mounting screws (Item #24). Remember the orientation 
of the pointer on Interlock Sleeve with respect to the switch position. The pointer must indicate that the receptacle is “OFF” when 
the disconnect switch is in the “OFF” position.

7. 

Replace the disconnect switch, with the same type as shown in Table 4, by reversing the steps above. Make sure to reconnect the 
wires to the same locations as before disassembly.

Table 4:  Disconnect Switch

Disconnect Switch Part Number

Ampere Ratings

Number of Poles

Horsepower

Appleton

Cuttler-Hammer

59301020100

DS36U

100 A

3

75

8. 

Torque the switch mounting screws to 25 in.- lb. to fasten the disconnect switch onto the switch base plate. Assemble the switch 
subassembly in the enclosure using the switch base plate screws with a torque of 25 in.- lb.

9. 

Torque the line and load pressure screws to 50 in.- lb. to hold the wires in place.

10. 

Conduct electrical tests. Refer to “Electrical Testing” on page 5 for details.

Terminal Block Interior

If applicable, tighten the terminal block lug screws to 50 in.-lb. torque for #2 AWG wire range (see Figure 7).

!

 WARNING

Failure to tighten the terminal block lug screws to 50 in.-lb. torque may result in over stressed wire terminations, which could cause 
the conductors to pull out of the terminal block and cause serious/fatal injuries due to electrocution.

Figure 3: Receptacle Phase Designation—3 Wire, 4 Pole

G

GROUNDING WIRE

GROUNDING WIRE

1

3

2

HALF MOON 

CONFIGURATION

TERMINAL BLOCK

LUG SCREW

Summary of Contents for FSQC 100

Page 1: ...engaged Arcing Confined Interlock receptacle design means that all electrical switching is done with an internal switch The plug cannot be engaged or disengaged with the receptacle when the switch is ON Positive Contact Brass contacts have integral springs for positive maintained electrical contact Receptacle face enables the engagement of plugs for a weatherproof union Positive Ground Grounding t...

Page 2: ... part of the receptacle appears to be missing broken or show signs of damage discontinue use immediately This condition could cause serious or fatal personal injury due to electrocution and or equipment damage Repair with the proper replacement part s before continuing service Warning environmental To prevent ignition of hazardous atmospheres do not use Class I Group F locations that contain elect...

Page 3: ...24 FACTORY WIRED 5 7 14 12 13 11 10 20 15 19 1 16 23 22 21 Table 1 Parts List Item Part Description Item Part Description Item Part Description Item Part Description 1 Receptacle Flip Cover 7 Switch Toggle 13 Switch Base Plate Screws 19 Ground Wire 2 Enclosure Cover 8 Line Side Pressure Screws 14 Sliding Plate 20 Fixed Plate 3 Locking Screw 9 Load Side Pressure Screws 15 Fixed Plate Screw 21 Screw...

Page 4: ...erring to Figure 2 turn the cover locking screw Item 3 clockwise inwards until it enters into the groove of the receptacle housing body Item 4 This makes the enclosure cover Item 2 free for rotation and simultaneously locks the receptacle interior rotation also toggling of the switch 2 Turn the enclosure cover counterclockwise outward to completely remove it from the enclosure 3 After removal we r...

Page 5: ...teps are completed 1 Test to verify correct phasing and ground connections 2 Test insulation resistance by meggering high voltage or hi pot test to ensure that the system does not have any short circuits or unwanted grounds Clean the Receptacle Cover Enclosure Before replacing or closing the receptacle cover it is strongly recommended that all dirt debris and other foreign materials be removed fro...

Page 6: ...th the P4 option have the interior rotated 22 1 2 degrees for special polarization applications They are compatible only with Appleton plugs with the P4 option Operating 1 Verify that the enclosed switch is in the OFF position The Arrow on the receptacle collar should be in line with the OFF marking on the nameplate 2 Align and insert the mating plug fully inside the receptacle Rotate the receptac...

Page 7: ...nations are secure Re torque to values given previously in these instructions if necessary NOTE Discoloration due to excessive heat is an indicator of possible problems and should be investigated and repaired as necessary 2 Check grounding and bonding effectiveness continuity Re torque connections to original values if necessary 3 Check gaskets for damage and replace as necessary 4 Inspect breathe...

Page 8: ...ch from its base plate by taking out the switch mounting screws Item 24 Remember the orientation of the pointer on Interlock Sleeve with respect to the switch position The pointer must indicate that the receptacle is OFF when the disconnect switch is in the OFF position 7 Replace the disconnect switch with the same type as shown in Table 4 by reversing the steps above Make sure to reconnect the wi...

Page 9: ...ew to 35 to 40 in lb torque Screw Cover Assembly 1 Referring to Figure 2 remove the screw Item 22 that fastens the end of the chain to the enclosure 2 Unscrew the screw cover assembly Item 21 from the receptacle housing 3 Replace the screw cover assembly by reversing the steps above See Table 5 for replacement part numbers 4 Torque the screw to 15 to 20 in lb Replacement Parts Table 5 Replacement ...

Page 10: ...ions FSQC receptacle and APJ plugs are classified for Class I Division 1 Groups B C and D Receptacles with the P4 option have the interior rotated 22 1 2 degrees for special polarization applications They are compatible only with Appleton plugs with the P4 option or Crouse Hinds plugs with the S4 option Appendix C Auxiliary Switch The auxiliary switch is designed for use with the appropriate monit...

Page 11: ...removing the two screws Item 15 Lift the plates up and slide them away from the switch actuator stud Item 11 2 Referring to Figure 4 mount the auxiliary switch Item 2 to the mounting bracket Item 1 using the two screws Item 3 3 Attach the mounting bracket to the disconnect switch using the existing screws 4 Adjust the location of the mounting bracket as needed to ensure that the auxiliary switch w...

Page 12: ...ies to any consumer While every precaution has been taken to ensure accuracy and completeness in this manual EGS Electrical Group LLC assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions Specifications are subject to change without notice The Appleton and Emerson logos are registered in the U S Patent and Trademark ...

Reviews: