Power Cable

(11) Cable Clamp Screw

 (3) Set Screw

(7) Washer

(8) Multi-Cut Grommet

(10) Locking Tab

(9) Bayonet Ring

Strip Length Jacket

(5) Insulator Block

(2) Front Housing

(1) Rear Housing

Solid Side

(4) Strain Relief

(6) Adjustable

Cable Clamps

 

NONMETALLIC POWERTITE

®

 PLUG SERIES 

WIRING INSTRUCTIONS 

 

WARNING:   BE SURE THE POWER IS OFF BEFORE STARTING INSTALLATION. 
 

 

READ ENTIRE DIRECTIONS BEFORE STARTING INSTALLATION.

 

CAUTION: 

Check to see that the rating label on the device is correct for the installation. 
Select cable/conductor of suitable ampacity, service type and temperature. See TABLE A. 

 

Figure 1

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

All installations must comply with applicable local code, National Electric Codes and/or Canadian Electrical Code. 

 

Table A 

 

 

Ampere 

Rating 

4W Cable Dia. Range 

Terminal 

Wire Range 

(Extra Flex) 

Strip Length (Fig. 2) 

Torque value 

Jacket 

Conductor 

Terminal 

Pressure Screws 

Strain relief 

nut (4) 

Cable Clamp 

Screw (11) 

 

inch 

AWG 

inch 

inch 

in.lb 

in.lb 

in.lb 

30 

0.45 – 1.12 for S, SO, STO 

G & W 

#12 - #6 

1.75 

0.7 

30 - 35 

min. 66 

18 

60 

0.50 – 1.45 for S, SO, STO 

G & W 

#8 - #4 

2.5 

0.9 

30 – 35 

min. 66 

35 

 

Figure 2

 

 

 

 

 

 

          

Figure 3

 

 
 
 
 
 

 
 
 
CAUTION 

The conductor size of the cord must be within the range specified in Table A. 

 

Use cable with diameters within the specified range given in Table A.  Failure to do so may result in 
overstressed wire terminations which could cause the conductors to pull out of the terminals and cause 
serious/fatal personal injury and/or equipment damage.

 

 
NOTE

:   

Plugs are to be used with Type G, W, S, SO, STO or equivalent "extra hard usage" portable cable w/copper conductors, 
per Table A and to National Electrical Code, Articles 400 and/or Canadian Electrical Code, Table 12.

  

 

 

 

 

 

 

Copper 

Conductors 

ONLY! 