APPLICATION: 

• Designed to  supply power  to  portable  or fixed electrical equip­

ment such as welders, infrared ovens batch feeders, conveyors

and truck and marine docks.

• Designed to supply three (3) phases grounded electrical power

to the aforementioned electrical equipment

• Designed to provide an interlocked receptacle for use in ordinary

( non-hazardous ) locations as defined in the  National Electric

Code ( NEC ). In additional the receptacle is designed such that

a mating plug can  only be  engaged  and  disengaged when

the switch handle is in the 

OFF 

position ..

• Ideal for use  on shipping docks, ports and other "ship to shore"

applications ..

• Suitable for use in locations that require a degree  of  protection

TABLE B 

"ACP" &  "CPH" PLUGS FOR  "WSR" RECEPTACLES 

CABLE 

PLUG 

DIAMETER  CURRENT  CATALOG 

(INCHES)  RATING 

NUMBER 

.390-1.375 

30 

ACP3034BC 

.500- . .875 

30 

CPH3034B 

,500-1.375 

60 

ACP6034BC 

,500- . .750 

60 

CPH6034A 

.750-1 .. 000 

60 

CPH6034B 

1.000-1..375 

60 

CPH6034C 

.390-1.375 

60 

CPH6034BC 

,,875-1..906 

100 

ACP1034CD 

from the elements  (NEMA Type  3,  3R or 12 for the  units  that  _________ 

have the receptacle flip cover installed and  ( NEMA Type 3, 3R,

4, 4X & 12 ) that  have  the  screw cover installed (  60 &  100 

Ampere only).

• Enclosure cover is gasketted to seal cover against the enclosure

housing ..

• The receptacle face of the 60 & 100 Ampere units is threaded to

allow mating plugs to thread onto it for a weather-proof  union ..

• WSR Series Interlocked receptacles may be pole mounted or

installed on flat vertical surfaces ..

TABLE C

TIGHTENING TORQUE 

DISCONNECT SWITCH LUG SCREWS 

WIRE SIZE 

TORQUE 

(AWG) 

(LB.-IN.) 

10-14

35 

8

40 

4-6

45 

0-3

50 

FIGURE  B 

CONTACT  PHASE IDENTIFICATION MARKINGS: 

Assembly View With Cover Removed  - Unit  Shown is Catalog  Number  WSR6352 

ELECTRICA L WARNING 

Electrical power MUST BE turned OFF before and during instal­

lation and maintenance. Failure to do  so may result  in seri­

ous/ 

fatal injury due to electrocution. 

GROUND  CONTACT 

Page 2 

330118  Rev"A"  3/29/95 

FUSE 

CLIPS 

LINE  CONT'ACT 

_____ 

,_ ____ IOENT'IFICA TION -

MARKINGS 

WIRE 

MARKER 

TYP 

GROUND  CONTACT-----

INTERLOCKED 

POWERTITE 

COMPATIBLE 

RECEPTACLE 

ASSEMBLY 

Summary of Contents for WSR Series

Page 1: ...s may result in serious fatal personal injury from electrocution TABLE A HORSEPOWER RATING FIGURE A Except as expressly provided by Appleton Electric Company Appleton in writing Appleton products are intended for ultimate purchase by industrial users and for operation by persons trained and experienced in the use and maintenance of this equipment and not for consumers or consumer use Appleton warr...

Page 2: ...90 1 375 60 CPH6034BC 875 1 906 100 ACP1034CD from the elements NEMA Type 3 3R or 12 for the units that _________ have the receptacle flip cover installed and NEMA Type 3 3R 4 4X 12 that have the screw cover installed 60 100 Ampere only Enclosure cover is gasketted to seal cover against the enclosure housing The receptacle face of the 60 100 Ampere units is threaded to allow mating plugs to thread...

Page 3: ...EW WITH COVER REMOVED UNIT SHOWN IS CATALOG NUMBER WSR6352 I 2 1 c e hc 2 Z lla 7 57 0 4 CATALOG ER CCf OUIT ENTRY r 1 1 11 00 27 9 CM WSR3352 WSR33342 WSR6352 WSR63542 WSRI03342 WSR10332 DIMENSION A 19 23 48 90 CM l 22 88 38 11 CM l A 330118 Rev A 3 28 95 Page 3 ...

Page 4: ... housing cover bolts 2 but do not attempt to remove them completely from the cover 3 because they are designed to be captive B The cover 3 is now free to swing open on its factory installed hinges 4 C Although it is not necessary the cover 3 can be removed fr om the housing 5 by carefully lifting the cover enough to clear the hinge pins approximately 90 inches D It is recommended that if removed t...

Page 5: ...nterior of all foreign materials 6 Cover bolts 2 must be tightened to25 30 lbs ft torque 7 Make sure that receptacle assembly flip cover 13 seals cover to receptacle housing face if applicable 8 Ifapplicable make sure that receptacle assembly screw cover 21 seals cover to receptacle housing face 9 Make sure the receptacle assembly nameplate located on the outside of the cover remains clean and leg...

Page 6: ...no unwanted opens shorts or grounds Do not apply power until the following steps are completed A Test to verify correct phasing and ground connections B Test insulation resistance by meggering high voltage or hi pot test to be sur e the system does not have any short cir cuits or unwanted grounds 7 CLEAN COVER AND HOUSING Before closing the cover 3 it is str ongly recommended that all dirt debris ...

Page 7: ...i JJ 1 Ii PW t WSRNT30F WSR3352 WSRNT30U WSR33542 WSRNT60F WSR6352 WSRNT60U WSR63542 WSRNTlOOF WSR10352 WSRNTlOOU WSR103542 Replace existing operating handle 11 with new one provided with disconnect switch group Re assemble housing lock out 12 and the two handle lock out screws 18 to housing 5 and tighten screws to 20 25 lb in torque C GROUND LUG Referring to FIGURE C loosen the ground lug screw a...

Page 8: ...sm assembly 2 down onto the line base assembly 3 until the tabs in the line base assembly lock into the corresponding holes in the mechanism assembly 2 Make sure switch mechanism 4 engages with switch pivot arm 5 Assemble the arc suppressor assembly 6 onto the line base assembly 3 with the arc suppressor retaining screw 7 provided For 30 60 Ampere fusible switches only Assemble fuse clips 8 to swi...

Page 9: ...cement parts To replace the receptacle assembly Referring to FIGURE C loosen the load side lug screws 9 ofthe disconnect switch 1 5 or fuse base 16 if applicable and remove wires Remove the four 4 receptacle assembly mounting screws 14 that fasten the assembly to the housing 5 Support the assembly so that it does not fall from unit Remove the old receptacle assembly and replace it with the new uni...

Page 10: ...mp 3w 4p WRDK1034 30 60 100 Ground lug screw assy 59350996000 WSR3352 WSR33542 WSR6352 WSR63542 WSR6352 WSR63542 WSR10352 WSR103542 WSR10352 WSR103542 WSR3352 WSR33542 WSR6352 WSR63542 WSR10352 WSR103542 WSR3352 WSR33542 WSR6352 WSR63542 WSR103542 WSR10352 WSR3352 WSR33542 WSR6352 WSR63542 WSR10352 WSR103542 WSR3352 WSR33542 WSR6352 WSR63542 WSR10352 WSR103542 Note For electrical interlock install...