background image

18 

4.0 MAINTENANCE 

If the duct furnace requires stopping to service, follow the section 3.0 on shutting 

the duct furnace down and starting up. 

4.1 Recommended Maintenance  

NOTE: The following recommended maintenance schedule should be followed every 6 
months unless otherwise specified below.  It is highly recommended to schedule the 
maintenance of the equipment in the spring and fall as equipment demands are commonly 
most critical after these periods and serve as good prevention practice.  
1.  Electrical - Check all wiring for loose connections.  Check voltage at the duct furnace 

(while in operation).  Check amperage draw against nameplate rating.  All contactors 
should be inspected to ensure that contacts are clean and are making good contact.  If 
contacts are pitted or burned badly, replace contactor points.  Single phasing and motor 
burnouts may result from bad contacts.  Check all fuses and replace blown fuses with 
equivalent size and type. 

2.  Gas Combustion - Check all fittings, valves and lines for leaks.  Check the burner; clean 

and adjust if necessary.  Check the flame sensor; clean if necessary.  Check the fuel 
supply pressure to the duct furnace and the manifold pressure. Check and clean the 
vent screen if necessary. Refer to burner manufacturer’s IOM for servicing the burner. 

3.  Controls - Clean and recalibrate all controls and check for proper operation.  Repair or 

replace any controls found faulty.  Check all damper controls and balancing points for 
fresh air requirements, tighten any linkages. 

4.  Motor Lubrication - Refer to motor manufacturer for lubrication recommendations.  On 

motors having grease drain plugs, remove the plugs and operate the motor for 15 
minutes before replacing plugs.  Do NOT over grease. 

Hours of Service 

Re-Grease Interval 

(Hours / Day) 

Up to 7.5 HP 

10 to 40 HP 

Over 40 HP 

Less than 12 

5 Years 

3 Years 

1.5 Years 

More than 12 

2 Years 

1 Year 

9 Months 

Motors that run in hot or severe dirt or wet conditions, should be greased at least every six 
months. 

5.  Furnace - Furnaces should be inspected at the beginning of heating season, and every 

4 months of usage under normal circumstances.  If the furnace is exposed to severe 
conditions where exposure to dust, soot, or other impurities contained in the air, a more 
frequent inspection is recommended.   

• 

Clean the burner wheel and rotate the wheel to ensure free movement and tightness 

• 

Check ignition spark and adjust if necessary 

• 

Inspect and clean ignition electrodes 

• 

Check flame supervisor relay flame signal 

• 

Inspect all safety controls and replace if necessary 

Summary of Contents for IFD SERIES

Page 1: ...If you smell gas 1 Open windows 2 Do not touch electrical switches 3 Extinguish any open flame 4 Immediately call you gas supplier WARNING Improper installation adjustment alteration service or maintenance can cause injury or death Read the installation operating and maintenance instruction thoroughly before installing or servicing this equipment This duct furnace must only be serviced by qualifie...

Page 2: ... 2 7 Exhaust Stack and Venting 8 2 8 Gas Installation 9 2 9 Electrical Installation 10 3 0 OPERATING INSTRUCTIONS 11 3 1 Start Up Check List 11 3 2 Combustion Operation 12 3 3 High Altitude Operation 13 3 4 Shut Down Instructions 14 3 5 Suggested Tools 14 3 6 Troubleshooting Guide 15 3 7 Final Checks And Adjustments 17 4 0 MAINTENANCE 18 4 1 Recommended Maintenance 18 5 0 4 2 Recommended Spare Par...

Page 3: ...ove information from this instruction manual Leave this instruction in the electrical enclosure of the duct furnace 3 Field installed fuel conversion kits are not available If your fuel requirements change contact the factory about converting your furnace to from natural or LP gas 1 2 Caution 1 Regulations require that service mechanics that work on combustion equipment must be qualified 2 Contact...

Page 4: ...d 3 The duct furnace is allowed to operate during building construction period 4 The duct furnace is installed without proper clearance to combustible materials or located in a confined space without proper ventilation for combustion See section 2 0 Installation 5 The duct furnace is operated in atmospheres containing flammable vapors chlorinated or halogenated hydrocarbons 6 The temperature rise ...

Page 5: ...se are continuously in use 2 1 Receiving and Storing 1 INSPECT the duct furnace carefully upon arrival for any shipping damage If damaged sign the carrier s bill of lading with a notation Damaged During Shipment or Received Damaged 2 Check the packing slip against all items received If any items are missing sign the carrier s bill of lading with the notation Shipment Received Less Item 3 When unlo...

Page 6: ...removed before lifting the duct furnace into place 6 If a fork lift truck is used caution must be taken to ensure that the forks do not damage the duct furnace or its components The forks must extend beyond the opposite side of the duct furnace to prevent damage 7 Check that there are or will be no explosive flammable or toxic vapors or abnormally excessive dust in the area where the duct furnace ...

Page 7: ...hanger and other components 6 If installing a duct furnace model IFD the furnace is connected to a return air duct or any other inlet air restriction the duct furnace shall be installed on the positive pressure side of the air circulating blower 7 When the duct furnace is installed in an enclosed duct furnace room it is imperative that the duct furnace room itself is not used as an air plenum Duct...

Page 8: ...air be ducted directly to the burner Refer to the relevant standards in the current CAN1 B149 1 CAN1 B149 2 B139 and Z223 1 in USA 2 7 Exhaust Stack and Venting 1 Installations must be in accordance with the requirements of authorities having jurisdiction Flue outlet pressure must not exceed rating on the name plate for maximum over fire pressure on positive fired chambers or maintain the over fir...

Page 9: ...ping to duct furnace and labeled for quick identification Color coding of pipe may be required and is recommended Carefully check the duct furnace rating plate for the fuel type supply pressure and input rating 2 Gas supply pressure higher than 14 w c 3 5kPa requires an additional field installed gas regulator Install the high pressure gas regulator and relief valve if supplied in the gas line to ...

Page 10: ...sumed to be the maximum load 2 Reconnect all disconnected wiring on the duct furnaces that were split for shipment 3 When connecting a power supply to a three phase motor take care that the three phase wiring gives you the correct motor and blower rotation on all motors 4 Should any original wire supplied with the furnace have to be replaced it must be replaced with wiring material having a temper...

Page 11: ...connect switch to OFF position 2 Close all duct furnace manual valves and field piping valves 3 Check the duct furnace supply discharge and vent to make sure they are clear and free from any obstructions Check to make sure all applicable dampers are open or adjusted to their correct settings 4 Purge all the air from the gas lines per gas codes Check all connections for leaks and correctness Ensure...

Page 12: ...ting up the duct furnace for the first time or if the duct furnace has been shut down for an extended period of time the same start up procedures as outlined in sections 3 2 and 3 3 should be followed 1 Refer to burner manufacturer s Installation Operation and Maintenance Instructions for proper set up operation and settings Turn on the main and pilot if applicable manual shutoff valves upstream o...

Page 13: ...gas control valve Check the nameplate for the correct pressure and adjust the appliance regulator if necessary b Check the CO and O2 reading at maximum and minimum inputs shown on the rating label O2 readings typically range from 4 10 CO readings should not exceed 400 PPM at any time Adjust the air gas ratios with the control linkages making fine adjustments before measuring again c Ensure proper ...

Page 14: ... automatically running the blower until the air reaches a cool enough temperature 4 Turn the duct furnace control to the OFF position 5 Set the main power disconnect to the duct furnace to the OFF position 6 Close the Main Manual Shut Off Valve if the burner is shut down for an extended period of time to prevent gas leaking into the combustion chamber 7 If the duct furnace is to remain idle for an...

Page 15: ...rrect rotation and or adjustment of switch C Flame safeguard relay goes into safety shutdown Lockout 1 See technical data sheets on flame safeguard relay 1 Determine the cause of lockout Reset the flame safeguard relay D Pilot does not light after pre purge has timed out and voltage is present on flame safeguard output terminals 1 Manual pilot shut off valve closed if applicable 2 Inlet gas pressu...

Page 16: ... inlet pressure 3 No gas on outlet side of butterfly valve or actuator with proper inlet pressure 4 Burner does modulate 1 Turn heat off on switch to the off position Slowly open all manual gas shut off valves 2 Clear obstruction in vent orifice or line Check for correct size spring Replace if defective 3 Check wiring voltage and adjustment Correct wiring or replace if defective 4 Check wiring and...

Page 17: ... manual gas valve before burner Operate unit in heat mode After pilot flame has been established close manual pilot gas valve if applicable The flame safeguard must trip out within 15 seconds Gas Pressure Switches The low gas pressure switch will trip out and must be reset before resuming operation when the inlet gas shut off valve is turned off or inlet gas pressure is lower than the trip point T...

Page 18: ...ld pressure Check and clean the vent screen if necessary Refer to burner manufacturer s IOM for servicing the burner 3 Controls Clean and recalibrate all controls and check for proper operation Repair or replace any controls found faulty Check all damper controls and balancing points for fresh air requirements tighten any linkages 4 Motor Lubrication Refer to motor manufacturer for lubrication rec...

Page 19: ...ber for carbon deposits soot scale or rust Clean if necessary If there is evidence of flame impingement a complete burner adjustment must be made Follow section 3 0 for all details referring to burner operation and start up 6 General Check for any vibration or unusual noise If any are observed locate the cause and correct Check the condensation lines for any blockages or leaks Check all piping and...

Page 20: ...20 5 0 SPECIFICATIONS The attached literature pertains to the specific duct furnace details ...

Reviews: