Installation and Service Manual – Metered Carbon Filter
Page 16
Copyright © 2012 Applied Membranes, Inc. All Rights Reserved.
Installer Displays and Settings (Continued)
Regeneration Settings
(7 Day Time Clock Option)
This menu will appear when the below is selected in step 3CS
STEP 1I
7
From normal mode, press NEXT +
▲
simultaneously for 5 seconds and release.
STEP 2I
7
Use
▲
or
▼
to set the current day of the week.
Default = 2 (Monday)
Press NEXT to go to the next step.
Press REGEN to exit.
STEP 3I
7
Display
Day of Week
day 1
d1
Sunday
day 2
d2
Monday
day 3
d3
Tuesday
day 4
d4
Wednesday
day 5
d5
Thursday
day 6
d
Friday
day 7
d7
Saturday
Scroll through the days 1 to 7 using “NEXT”. Use
▲
or
▼
to turn regeneration on
or off for each individual day.
When “
◄
” indicator is displayed next to “Regen”,
regeneration is ON for that day. When there is no indicator, regeneration is OFF for that day.
After completing the 7
th
day, press NEXT to go to the next step.
Press REGEN to go to previous display.
STEP 4I
7
Regeneration Time Hour: Set the time of day for regeneration to occur by pressing
▲
or
▼
.
Press NEXT to go to the next step. Press REGEN to go to the previous step.
STEP 5I
7
Regeneration Time Minutes: Set the time of day for regeneration to occur by
pressing
▲
or
▼
. Press NEXT to go to the next step.
Press NEXT to exit Installer Displays and Settings.