VENTILATOR LOCATION AND ORIENTATION
If the outlet of the ventilator is not ducted, or if small sections of
collapsible duct (i.e. flex duct) are attached to the outlet, then
the ventilator must be mounted in a location which minimizes
interference with moving parts (see
CAUTIONS
below)�
CAUTION
1.
Mount the blower with the lowest, exposed moving parts
at least 8 feet (2.4 m) above floor or grade level.
2.
Mount the blower at least 3.3 feet (1.0 m) from any
accessible opening of the duct.
Choose a location for the ventilator that is within 6 feet of the
outlet into which the ventilator will be plugged� Allow space for
filter removal and service as shown in
FIGURE 2
�
The ventilator can be mounted in any orientation�
12”
FILTER
ACCESS
24”
FAN
ACCESS
90-2514
FIGURE 2
– CLEARANCES FOR SERVICING
INSTALL ELECTRICAL OUTLET
Install a standard NEMA 5-15 receptacle suitable for the location, near where the ventilator will be installed� The ventilator comes
equipped with a 6-foot power cord with a standard 3-prong plug�