background image

TROUBLESHOOTING

DISPLAY IS BLANK 

If Power LED is not illuminated at the equipment 
control module check the following:
•  Check circuit breaker and reset if necessary .
•  Make sure power switch at heating & cooling 

system is on .

•  Make sure furnace door is closed securely .

HEATING SYSTEM DOES NOT RESPOND 

(“HEATING” APPEARS ON SCREEN)

•  Check for 24VAC at the equipment on the secondary 

side of the transformer between power and 
common . If voltage is not present, check the heating 
equipment to find the cause of the problem .

•  Check for 24VAC between the heat terminal (W) 

and the transformer common . If 24VAC is present, 
the thermostat is functional . Check the heating 
equipment to find the cause of the problem .

•  Check for loose or broken wires between the 

thermostat and the heating equipment .

COOLING SYSTEM DOES NOT RESPOND 

(“COOLING” APPEARS ON SCREEN)

•  Check for 24VAC at the equipment on the secondary 

side of the transformer between power and 
common . If voltage is not present, check the cooling 
equipment to find the cause of the problem

•  Check for 24VAC between the cooling terminal (Y) 

and the transformer common . If 24VAC is present, 
the thermostat is functional . Check the cooling 
system to find the cause of the problem .

•  Check for loose or broken wires between the 

thermostat and the cooling equipment .

FAN DOES NOT TURN ON IN A CALL FOR HEAT

•  Check Installer Setting 

Fan Control In Heating / 

Heat Pump Auxiliary Type

, to make sure the fan 

control is properly set to match the type of system .

HEAT PUMP ISSUES COOL AIR IN HEAT MODE, 

OR WARM AIR IN COOL MODE

•  Check wiring at the terminal block to confirm the 

reversing valve is connected to the proper terminal . 
O is active in cooling and B is active in heating .

HEAT/COOL BOTH ON AT SAME TIME

•  Check Installer Setting 

Equipment Type

, to make 

sure it is set to match the installed heating/cooling 
equipment .

•  Check to make sure heating and cooling wires are 

not shorted together .

HEATING EQUIPMENT IS RUNNING IN  

COOL MODE

•  Check Installer Setting 

Equipment Type

, to make 

sure it is set to match the installed heating/cooling 
equipment .

“HEATING” IS NOT DISPLAYED

•  Check Installer Setting 

Control Setup

 is set 

correctly .

•  Change the System Mode to Heat, and set 

the temperature level above the current room 
temperature .

“COOLING” IS NOT DISPLAYED

•  Check Installer Setting 

Control Setup

 is set 

correctly .

•  Change the System Mode to Cool, and set 

the temperature level below the current room 
temperature .

INSTALLER MENU

USB SETTINGS 

FILE IMPORT, ETC

THERMOSTAT & 

HVAC SYSTEM 

CONFIGURATION

HUMIDIFIER 

CONFIGURATION

DEHUMIDIFIER 

CONFIGURATION

EQUIPMENT 

OUTPUT TESTS

IMPORT/EXPORT 

USB INSTALLER 

SETTINGS FILES, 

FACTORY RESET

VENTILATION 

CONFIGURATION 

AIR CLEANER 

CONFIGURATION

QUICK REFERENCE TO CONTROLS & DISPLAY

POWER/STATUS

 – On solid during normal operation . Flashes 

when connection to the thermostat is lost and at power-up while 
the thermostat connection is being established .

HEATING

 – On when heating outputs are active .

COOLING

 – On when cooling outputs are active .

FAN

 – On when fan output is active .

HUMIDIFIER

 – On when humidifier output is active .

DEHUMIDIFIER

 – On when dehumidifier output is active .

VENTILATION

 – On when ventilation output is active .

AIR CLEANING

 – On when air cleaner output is active .

EQUIPMENT CONTROL MODULE LEDs

THERMOSTAT FEATURES

•  Remote access and control over Wi-Fi .
•  Indoor air quality control . 

– Humidification automatic or manual control . 
– Dehumidification . 
– Event-Based

 air cleaning . 

– Ventilation with temperature and humidity limits .

•  Temperature control .
•  Heat Blast

®

 raises the room temperature 3°F to 5°F .

•  One touch Away .
•  Support for optional wireless outdoor temperature 

sensor .

•  Large touch screen with adjustable backlight .
•  7 day programmability . 

•  Displays room temperature, room humidity, 

temperature setting, and optional outdoor temperature .

•  Air filter, humidifier, dehumidifier, and HVAC service 

reminders .

•  Programmable fan control with fan circulation mode .
•  Easy to use temperature control can override program 

schedule at any time .

•  Progressive recovery ensures proper temperature at 

the start of a program event .

•  Built in compressor protection prevents damage to 

your equipment .

•  System test mode .

English

 19

18 

English

Summary of Contents for 8920W

Page 1: ...bles 10 12 General system settings table 10 Thermostat system settings table 11 12 Indoor Air Quality system settings tables 13 16 Humidifier system settings table 13 14 Dehumidifier system settings table 14 Air cleaning system settings table 15 Fresh air system settings table 15 16 Installer system test 16 Wi Fi setup 16 Quick reference to controls display 17 18 Thermostat features 18 Troubleshoo...

Page 2: ...perature sensor should be mounted On an interior wall in a frequently occupied space Approximately 5 above floor At least 18 from outside wall Using less than 300 of wire Do not mount remote sensor Behind doors in corners or other dead air spaces In direct sunlight near lighting fixtures or other appliances that give off heat On an outside or unconditioned area wall In the flow of a supply registe...

Page 3: ...2 sensor to the ODT terminals and enabling the outdoor sensor in the installer setup menu When an outdoor sensor is installed the features below will be enabled In heat pump mode the outdoor temperature sensor can be used to efficiently utilize an air source heat pump When the outdoor temperature is less than the Low Balance Point the heat pump will be locked out and only auxiliary heating will be...

Page 4: ...OLING LOCATE SENSOR IN SHADED AREA CONVENTIONAL HEAT COOL TWO TRANSFORMER REMOVE JUMPER HEATING TRANSFORMER COOLING TRANSFORMER C R W W2 B Y Y2 O G L RH RC C 3 EQ HP HC G Y3 Y2 Y W3 W2 W TRANSFORMER THERMOSTAT 1 2 2nd COOLING 1st COOLING FAN 1st HEATING 2nd HEATING 3rd HEATING 3rd COOLING 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source 1 RE...

Page 5: ...FAULT DETECT REVERSING VALVE REVERSING VALVE 2nd HEATING 1st HEATING FAN 1st COMPRESSOR 2nd COMPRESSOR 2 1 1 R and C can be powered from the HVAC equipment transformer or any other constantly powered 24VAC source INDOOR AIR QUALITY WIRING DIAGRAMS INDOOR AIR QUALITY WIRING WITH SEPARATE TRANSFORMERS INDOOR AIR QUALITY WIRING WITH A SINGLE TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER VNT DH HUM ...

Page 6: ...compressor stages Heat Pump mode only One Two Number of Auxiliary Heat Stages Select number of auxiliary heat stages Heat Pump mode only One Two Number of Stages of Heat Select number of heat stages Heat Cool mode only One Two Three Number of Stages of Cool Select number of cool stages Heat Cool mode only One Two Three Remote Temperature Sensor Installed Select if the remote sensor is attached and...

Page 7: ...ettings are only present dependent upon the value of other settings The use of an outdoor temperature sensor recommended enables additional Indoor Air Quality functionality Please refer to the Model 8920W Owner s Manual for further information about thermostat features Note Refer to manuals for humidifier dehumidifier air cleaner and ventilation products for recommended installation and operation ...

Page 8: ...y default setting bold and setting range Fresh Air Vent Installed Selects if ventilation is installed If set to No no other ventilation settings will be available No Yes Display Button Note only available if Fresh Air Installed is set to No Yes No Fresh Air Setup Type Selects if ventilation is configured through the Code setup or Comfort Comfort setup has more lockout options Code setting ensures ...

Page 9: ...MPERATURE SCALE LOCKOUTS AWAY MODE SETTING IF ENABLED AWAY MODE STATUS IF INSTALLED FAN MODE SELECTION CLEAN DISPLAY TOUCHSCREEN IS OFF FOR 30 SECONDS ROOM TEMPERATURE HUMIDITY HEAT SETTING THERMOSTAT NAME System setting Description Factory default setting bold and setting range Enable Low Vent Temperature Limit Enables low ventilation temperature lockout limit Only available if Outdoor Sensor is ...

Page 10: ...ting Equipment Type to make sure it is set to match the installed heating cooling equipment HEATING IS NOT DISPLAYED Check Installer Setting Control Setup is set correctly Change the System Mode to Heat and set the temperature level above the current room temperature COOLING IS NOT DISPLAYED Check Installer Setting Control Setup is set correctly Change the System Mode to Cool and set the temperatu...

Page 11: ... to 50 R H Dehumidification 40 to 90 R H SPECIFICATIONS Electrical Operating voltage 24VAC 18 30VAC Current Maximum 2 5A total 1 0A single output Maximum surge current 5A Environment Temperature shipping 30 to 150 F 34 to 65 C Temperature thermostat operating 32 to 120 F 0 to 48 C Temperature equipment control module operating 32 to 158 F 0 to 70 C Relative humidity Operating 5 to 90 R H non conde...

Reviews: