ENGLISH
65
SETTINGS
PARAMETERS
VALUES
DESCRIPTION
Config
Disabled
External Control Disabled
Enabled
External Control enabled and
Timers A-H disabled
Override
External Control enabled with
priority over the enabled Timers
A-H
Origin speed
Digital IN
Speed determined by the state of
the digital inputs.
0-10 V
Speeds determined by 0-10V
analog voltage signal (see chapter
2.5)
4-20mA
Speeds determined by 4-20 mA
analog current signal (see chapter
2.5)
X1
The speed X1 set in the "External
Speeds" menu is implemented.
E.ADAPT
Speed determined by the status of
the inputs of the "E.ADAPT"
module
Start Input
IN-0
Starting of the pump is
determined by the status of input
IN-0.
Speed
Pump starting determined by the
status of inputs IN1-4. Without
Speed Mode
Priority
Each input is associated with a
speed (IN1 --> X1; IN2 --> X2;
etc.);
in the case of more than one
enabled input, the one with the
highest number
(IN4>IN3>IN2>IN1) has priority.
Combinations a speed according to table X is
associated with each combination
of inputs IN1 and IN2
IN1 (0) + IN2 (0) --> SPEED (X1)
IN1 (1) + IN2 (0) --> SPEED (X2)
IN1 (0) + IN2 (1) --> SPEED (X3)
IN1 (1) + IN2 (1) --> SPEED (X4)
NOTE:
In case of Speed Mode = Priority, speeds X1-X4 are available.
In case of Speed Mode = Combination, speedsX1 is not available.
In case of Start Input = Speeds, X1 is not enabled and the combination 0 0 does not cause the pump to start.
INPUTS
PARAMETERS
VALUES
DESCRIPTION
IN0-IN4 Type
NO
Normally Open
NC
Normally Closed
OUTPUT
PARAMETERS
VALUES
DESCRIPTION
Config
RUN
The relay signals when the pump
is working