SECTION 3: MAINTENANCE

The media in this the APUN Series Upfl ow Acid Neutralizer System is sacrifi cial, therefore it must be replenished periodically. 

The frequency is 

dependent on the raw water pH and your water consumption habits. The lower the pH and the higher the water usage, the more frequently 
replenishment will be required. One easy way of determining when to replenish is by placing a mark on the outside of the tank at the level 
of the media when fi rst installed. Periodically shine a bright light through the tank and compare the current level to the mark, if it is down 
more than two (2) inches, add media to the mark. If you are unable to see through the tank, remove the fi ll-port cap and measure down 
to the top of the media. The tank should be 2/3 full. If not, add media. 

REPLENISHING MEDIA:

1)  Close inlet and outlet valves. Open bypass valve so untreated water can still be used during the replenishment operation.

2)  Open boiler drain to relieve pressure. Remove fi ll-port cap using wrench provided, some water will drain out of the fi ll-port opening. Use 

a fl exible tube to siphon approximately two gallons of water from the tank.

3)  Using the funnel provided, add the required amount of media, not to exceed the indicated line on the media tank. A bright light may be 

placed behind the tank to observe the media level.

4)  Refer to Steps 8-9 in  Section 2 for fl ushing instructions to complete the replenishment operation.

Figure 4.  ADDITION OF NEUTRALIZER MEDIA

Add media through fi ll-port using funnel

Summary of Contents for APUN100-LM

Page 1: ...ON AND OPERATING INSTRUCTIONS APUN SERIES UPFLOW ACID NEUTRALIZERS MODELS APUN101 APUN201 APUN301 APUN100 LM APUN200 LM INSTR2195 0412 Installer please leave with homeowner Homeowner retain for future...

Page 2: ......

Page 3: ...old water system as an electrical safety ground a jumper must be used to ensure a sufficient ground connec tion across the Acid Neutralizer System installation piping refer installation to qualified p...

Page 4: ...stem cartridges plastic fittings or plastic plumbing On plastic fittings never use pipe sealant or pipe dope Use PTFE thread tape only pipe dope properties may deteriorate plastic Take care when using...

Page 5: ...the pH is approximately 5 5 6 0 units The neutralizer media dissolves when water with a low pH passes through The blend is used to take advantage of the fast vigorous pH adjusting capabilities of mag...

Page 6: ...d position until instructed otherwise CAUTION To reduce the risk associated with property damage due to water leakage Installation and use MUST comply with existing state or local plumbing codes Mount...

Page 7: ...in Open boiler drain and slowly open inlet valve to flush the APUN Series Upflow Acid Neutralizer System Discharge water from hose will be milky white due to fines generated during shipping and handli...

Page 8: ...through the tank remove the fill port cap and measure down to the top of the media The tank should be 2 3 full If not add media REPLENISHING MEDIA 1 Close inlet and outlet valves Open bypass valve so...

Page 9: ...onnect the plumbing attached to the bypass valve first Then rotate the fill port head assembly to the left or counter clockwise Before attempting any disassembly pressure should be relieved by shuttin...

Page 10: ...flow Distributor Tube 6236435 6236435 6236435 6236435 DF37 69 4 Media Calcium carbonate N A C 050P N A C 050P x4 C 050P x6 5 Gravel 1 4 x 1 8 N A QC 18 N A QC 22 QC 22 6 Funnel U1006 U1006 U1006 U1006...

Page 11: ...8 V3152 O ring 135 2 9 V3155 O ring 112 2 10 V3156 O ring 214 2 V3191 01 Vertical Adapter Assembly 6 5 6 5 4 1 4 1 1 2 3 3 1 2 Order No Description Quantity V3151 Nut 1 Quick Connect 2 V3150 Split Ri...

Page 12: ...tion shall be at 3M Purification Inc s option to replace or repair the Product or refund the purchase price of the Product This warranty does not cover labor The remedy stated in this paragraph is Cus...

Reviews: