AS Control Plus         02-2019 EN

TOP-UP (factory setting 90 minutes)

By pressing the OK key you can select whether the top-up with fresh water should be time-controlled 

or whether the top-up is switched ON or OFF. If the top-up is time-controlled, you can set the time 

limit for the top-up between 1 and 999 minutes. If the time limit has been reached and the water level 

has not reached its set height, there is a problem with the top-up system. The top-up switches off and 

the override alarm is triggered.

BACKWASH WITH FORCED START (factory setting OFF)

Here you can select automatic backwash in the case of forced start. In this way you can avoid too 

much water from draining away needlessly via the safety overflow. The water can then be used again 

for another backwash. Backwash can also be useful when heavy rain causes the overflow channel to 

be switched on, thus causing an unnecessary waste of energy. The delay time for the backwash can 

be set between 1 and 200 minutes.

GENERAL ALARM: RUN-DRY PROTECTION (factory setting OFF)

By pressing the OK key you can select whether to trigger the general alarm in the case of a run-dry 

situation. If you activated the general alarm, you can select a delay time of between 0 and 200 minu-

tes. When this time has expired, the general alarm is triggered and a warning text appears in the blue 

display panel.

COLLECTVE ALARM: FORCED START

By pressing the OK key you can select whether to trigger the collective alarm in the case of a forced 

start situation. If you activated the general alarm, you can select a delay time of between 0 and 200 

minutes. When this time has expired, the general alarm is triggered and a warning text appears in the 

blue display panel.

OVERFLOW TANK MENU:

MAIN DRAIN AT DRY RUN PROTECTION (Factory settings: OFF)

The «Besgo» valve switches to main drain to avoid stopping the filtration 

pump because dry running (empty overflow tank). 

By pressing the OK key you can select this function ON and OFF. 

By pressing the OK key you can select whether overflow operation is triggered when a specific  

ambient air temperature is reached or when a specific temperature difference between ambient  

air and water temperatures is reached.

a) Set temperature:

 until the set temperature for air is reached, the system remains in economy 

mode (no current to the Besgo valve - drained directly from the pool). Only when the set temperature 

has been reached does the Besgo valve switch to overflow mode. Setting 5 °C to 40 °C. When solar 

covers are being used we recommend the use of the set temperature. The set temperature should  

be set no higher than 20 °C. At a temperature of 20 °C in the shade, there is considerable solar gain 

from the cover which is stored up under the cover in economy mode. Temperatures under the cover 

can reach as much as 50 °C and more. This heat accumulation must be dissipated via the overflow 

channel.

b) Temperature difference:

 You can set a temperature difference of b10 °C and -10 °C.  

For example, if a temperature difference of +2 °C is set, then the Besgo valve switches to operation 

via the main drain if the air temperature is 2 °C higher than the water temperature. If a temperature 

difference of -2 °C is set, then the Besgo valve only switches if the air temperature is 2 °C lower than 

the water temperature.

CAUTION: (liability exclusion)

Some pool manufacturers (polyester, liner) limit their warranty to use at temperatures of 30 to 35 °C. 

Potential damage to such pools or their covers is not covered by us

.

ECO PROGRAMME MENU:

ECO PROGRAMME MODE

(factory setting: set temperature 20 °C, hysteresis 1 °C

Summary of Contents for AS Control Plus

Page 1: ...Operating Instructions AS Control Plus 2019 English ...

Page 2: ...0 C water temperature in Switzerland we were able to demonstrate an energy saving of more than 20 000 kW equivalent to 2 000 litres of oil in a six month period May to October Suction Overflow tank Suction pool Main drain Suction pool Auto Overflow protection Top up solenoid valve Run dry protection Cover closed ON FAULT Backwash aktive Suction Overflow tank Level probes Overflow tank Operating ke...

Page 3: ...ckwas from the pool or the overflow tank 6 Energy efficiency control economy or overflow Operation 7 Shortcut for starting a backwash and changing the heating setpoint 8 All data for the previous ten month period are stored These can be downloaded onto a PC for analysis 9 Optional flow control with a paddle switch Technical data Connectors 78 connectors for inputs and outputs Relays 13 relays Elec...

Page 4: ...re is a large amount of heat loss evaporation convection During operation with the pool covered open the pool water has to be circulated via the overflow 2 Economy mode In so called economy mode water is drained directly from the pool i e from one or more drains Pool pump pool Thus the water no longer flows via the overflow The heat loss is reduced considerably Economy mode is best suited to perio...

Page 5: ...nage will take place directly via the pool economy mode or via the overflow channel As soon as the pool cover is opened the system goes into overflow mode The limit switch must be connec ted to terminals 71 72 2 Main drain operation economy mode The Besgo valve is always in the economy mode and drainage is via the main drain irrespective of temperature and whether the pool cover is open or closed ...

Page 6: ...the overflow for at least 30 to 60 minutes per day Only in this way can you measure and control the water level the measurement takes place in the overflow tank Additionally the correct water flow via the overflow channel will be re established by entering the times for the overflow operation which will ensure proper circulation within the pool With public pools we recommend switching to over flow...

Page 7: ... the day of the week changed or an interval of 1 to 30 days between backwash cycles chosen by means of the arrow keys BACKWASH VIA factory setting overflow tank By pressing the OK key you can select by means of the arrow keys whether the backwash takes place via the overflow tank or the main drain DELAY STOP VIA OVERFLOW factory setting 30 minutes After every backwash there is a compulsory flow vi...

Page 8: ...e blue display panel OVERFLOW TANK MENU MAIN DRAIN AT DRY RUN PROTECTION Factory settings OFF The Besgo valve switches to main drain to avoid stopping the filtration pump because dry running empty overflow tank By pressing the OK key you can select this function ON and OFF By pressing the OK key you can select whether overflow operation is triggered when a specific ambient air temperature is reach...

Page 9: ...EMPERATURE CORRECTION By pressing the OK key you can adjust by means of the arrow keys the actual air temperature shown in the blue display by up to 10 C to 10 C This fine adjustment is useful when there is a difference between the measured and actual pool temperature due to the positioning of the temperature probe TEMPERATURE PROBE AIR factory settings ON By pressing OK you can enable or disable ...

Page 10: ...r on the pool closed limit switch contact Priorities The overflow filter time always has priority over other actions This means that when the unit is operating via the main drain in economy mode and the overflow filter times are active the controls switch to normal operation With the same objectives the following priorities are active Im gleichen Sinn sind folgende Prioritäten vergeben 1 Overflow ...

Page 11: ...02 2019 EN AS Control Plus 11 Caution Only 1 filter pump can be connected 230 VAC or 400 VAC Wiring diagram Art No 081190 ...

Page 12: ...Badu Prime Art No 034110 with Speck Badu Delta Art No 034113 with Speck Badu Profi Art No 034101 with Speck Badu Alpha Art No 034112 Backwash 36 37 Filter operation via Overflow tank Filter operation via main drain Wiring diagram Art No 081190 ...

Page 13: ...entair IntelliFlow VSD and control IntelliCommII Art No 034001 Art No 034006 Level 4 Level 3 Level 2 Level 1 Wiring diagram Art No 081190 Wiring diagram Wiring diagram 02 2019 EN AS Control Plus 13 10 9 8 7 6 5 4 3 ...

Page 14: ...with pump UWE EO PM Art No 037000 Control cable GND Wiring diagram Art No 081190 14 AS Control Plus 02 2019 EN ...

Page 15: ...with frequency converter AS ATV 212 Art No 036120 036129 F R RES PLC P24 CC FM PP VIA VIB CC Wiring diagram Art No 081190 02 2019 EN AS Control Plus 15 ...

Page 16: ...with frequency converter Invertec Optidrive E2 1 2 3 4 5 6 7 8 37 38 Wiring diagram Art No 081190 16 AS Control Plus 02 2019 EN ...

Page 17: ...17 AS Control Plus 02 2019 EN Menu layout with ...

Page 18: ...02 2019 EN AS Control Plus 18 ...

Page 19: ......

Page 20: ......

Reviews: