background image

 

User Manual Thermal X - R Series Chillers   

 

 

 

 

 

Page 15 

Pump Delay Time 

The controller will wait for a certain time before taking flow reading – it is designed to give the ball 

valve time to open before indicating flow problems 

Tandem Control 

One chiller will need to be assigned a master chiller and the other a slave chiller – see “CHANGING 

THE CONTROLLERS PARAMETERS” section for instructions on doing this. The master chiller 

will do all the controlling and timing. OUT8 (Standby: Tandem link enable/ Status) on the control 

board will be energised while it is running closing the indicated input (enable) on the standby chiller 

not allowing it to run. After a week the output will de-energise and the standby chiller will run – its 

OUT8 energising closing the input on the now standby chiller. 

Close Tolerance 

If the unit has been manufactured for close tolerance then the controller will attempt to keep the water 

temperature  within  the  close  tolerance  range  around  the  midpoint  between  the  set  point  and  the 

hysteresis.  

 

For example if the set point is 10°C, the hystersis 2°C and the close tolerance 1°C then the controller 

will attempt to keep the temperature between 10.5°C and 11.5°C. The ability of the chiller to keep 

the temperature as close to the set point will vary depending on heat load. The closer the heat load is 

to the chillers rated capacity the more accurate the chiller can maintain the close tolerance. Under low 

loads the chiller will be unable to maintain less that 1°C close tolerance.  

Putting the unit in standby mode 

Using the key pad the unit can 
be put into standby mode if 
there is a reason to shut the 
unit down for a short amount 
of time.  

 

Scroll through the menu to find “KEYPAD STANDBY” 

 

Press “OK” and then “OK TO CONFIRM” The unit will stop running 

 

The screen will be showing “OK TO RE-START” and “KEYPAD 
STANDBY MODE” will be flashing 

 

Press “OK” and the chiller will go through its normal start up 
procedure

 

Note: This does not turn the unit off and the electrical circuitry inside the electrical box will still be live. 

Chiller achieves close tolerance control by using Aqua Cooler PCB to collect high pressure and low 

pressure data. PCB uses collected data to calculate suitable hot gas amount and send signal to hot gas 

solenoid valve.  

Summary of Contents for Thermal X R Series

Page 1: ...s Page 1 Revision 2 AUGUST 2019 Thermal X R Series Owner s Manual This guide applies to the following models R150 to R4000 Aqua Cooler Pty Ltd U14 2 12 Knobel Court Shailer Park 4128 Qld www aquacoole...

Page 2: ...ng Sequence 9 Operating Precautions 9 CHLF2 60 10 CHLF4 60 10 CHLF12 40 11 CDMF20 4 11 CDMF32 30 12 Aqua Cooler Controller 12 Unlocking the Keypad on the Aqua Cooler Controller 12 Operational Logic of...

Page 3: ...chematic 24 Poor Heat Dissipation 26 Low Refrigerant 26 Low and High Pressure Difference 27 Compressor Not Starting 27 Maintenance 27 Recommended Preventative Maintenance Program 28 Warranty 28 Genera...

Page 4: ...process cool They are supplied with an immersed coiled evaporator or plate heat exchanger or shell tube evaporator model dependant an air cooled condenser and a rotary or scroll compressor to circula...

Page 5: ...ould be secured to prevent it from toppling over Minimum temperature setting is 5 C on the unit Any lower than this may cause problems with the evaporator icing up and potentially loss of refrigerant...

Page 6: ...possible If the unit is to be stored before installation then care must be taken to ensure no foreign matter can get into the water pipes If the storage is for a prolonged period it is recommended tha...

Page 7: ...ort the chiller s full operating weight Installation of the Water Path Before connecting the make up water check the suction pressure on in the chiller to ensure there is no refrigerant leak A refrige...

Page 8: ...ltage at the chiller under all load conditions Three phase power must be symmetrical ensuring equal effective voltage and equal phase angle between consecutive phases The pump and the compressor rely...

Page 9: ...oints and operational parameters are displayed on the screen Any faults are indicated on the face of the control panel It is a good idea after the unit has been running for 5 minutes check that the wa...

Page 10: ...R230 R300 R330 CHLF2 60 R420 R540 R670 R830 R1000 R1200 R1330 CHLF4 60 R1500 R2000 R2500 CHLF12 40 R3000 CDMF20 4 R4000 CDMF32 30 CHLF2 60 Model Driving Motor Q 3 0 5 1 0 1 5 2 0 2 5 3 0 3 5 CHLF2 60...

Page 11: ...12 40 Model Driving Motor Q 3 7 8 9 10 11 12 13 14 15 16 CHLF12 40 2 4 3 3 H 47 46 45 43 5 41 5 39 5 37 5 35 31 5 27 5 CDMF20 4 Model Driving Motor Q 3 0 10 12 14 16 18 20 22 24 26 28 29 CHLF12 40 5 5...

Page 12: ...7 AQUA COOLER CONTROLLER The chiller unit features an interface panel with LCD display and input buttons to configure certain functions of the unit Unlocking the Keypad on the Aqua Cooler Controller T...

Page 13: ...eratures too high or too low Temperature Control High and Low Temperature Alarm Stop High and low temperature limits can be set in order that if they are breached then the chiller will shut down In ra...

Page 14: ...et to run if the chiller develops a fault by turning this feature ON in the program will keep water to the process This water will of course get warm but it is designed to keep the process cool long e...

Page 15: ...the set point is 10 C the hystersis 2 C and the close tolerance 1 C then the controller will attempt to keep the temperature between 10 5 C and 11 5 C The ability of the chiller to keep the temperatur...

Page 16: ...ER TEMP will show Press the escape key to revert to home page Temperature Hysteresis Temperature between refrigeration circuits cut out and cut in Scroll to the PARAMETERS MENU then to the SET POINTS...

Page 17: ...by pressing the OK button Range Low 5 C to 10 C High 10 C to 40 C Scroll to PARAMETER MENU and to the SET POINTS sub menu Scroll to HIGH TEMP ALARM and LOW TEMP ALARM and press OK SET HI TEMP ALARM wi...

Page 18: ...nded that the setting is not greater than 1 or 2 minutes Tandem Installation Assigning the chillers into a single or tandem set installation Scroll to PARAMETER MENU and then to the SYSTEM sub menu Sc...

Page 19: ...allation YES on master chiller in N 1 installation VAR SPEED FUNCTION OFF On for chillers fitting with VFD on compressor or the pump NO HE SENSORS 0 LOW TEMP STOP YES AUX INPUTS N O FAN SPEED CONTROL...

Page 20: ...RM 1 0 1 L s MAX TEMP LIMIT 20 SUPPLY FLOW WARNING 1 Varies with pump supplied SET PT AMB OTEMP 45 SET POINT TEMP Customer Specific SENSOR MENU CCT1 SUCT PR SIZE 0 10 Bar SECONDARY SUPPLY CAL See Proc...

Page 21: ...vice Number 2012 ModBus RTU Slave Addr 1 247 head in the Chiller ID tab Again use the save password aquacustomer as the password 7 Then edit the page to the new IP address details for the chiller agai...

Page 22: ...e approximately 3 weeks of data logging 10 second intervals will only give 24 hours of data logging and the logging drops the old files off the end so if the unit has a problem and it takes more than...

Page 23: ...ted to the internet or to a BMS system the BIN file will need to be updated as well to the corresponding issue number Using a laptop connect to the Aqua Cooler controller via the Ethernet card in the...

Page 24: ...oss the bottom of the board IN1 NOT USED IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 Not Used 0 10V Input 0 10V NC Input 0 10V NC Input 0 10V NTC thermistor 0 10V NTC thermistor 0 10V NTC thermistor 0 10...

Page 25: ...no other equipment in the vicinity that may be throwing heat onto the unit or that the unit has not been installed improperly Faulty HP transducer or HP switch replace Low pressure LP alarm tripping F...

Page 26: ...ck operation of transducer reading correctly Low refrigerant charge Check refrigerant system operation check super heat and sub cooling are with in normal operating ranges High Ambient Temp Faulty pro...

Page 27: ...pressure switch is damaged 5 The overload protector of the compressor is damaged 6 The electromagnetic relay is damaged or the overload protector is damaged 7 The water level is too low 8 The refrige...

Page 28: ...be excluded under Australian Consumer Law You are entitled to replacement or refund for a major failure and to compensation for other reasonably foreseeable loss or damage You are also entitled to ha...

Page 29: ...User Manual Thermal X R Series Chillers Page 29 Installation Sketch Map of Air Cooled Chiller...

Page 30: ...User Manual Thermal X R Series Chillers Page 30 Installation Sketch Map of Water Cooled Chiller...

Page 31: ...User Manual Thermal X R Series Chillers Page 31 Internal Structure Sketch Map of Air Cooled Chiller...

Page 32: ...User Manual Thermal X R Series Chillers Page 32 Internal Structure Sketch Map of Water Cooled Chiller...

Page 33: ...of the completed table and send it back to us Customer and On Site Requirement Required Capacity kW Rated Ambient Temp C Rated Supply Temp C Rated Flow Rate L s Customer Address Machine Information C...

Page 34: ...NO Ambient Temp C Water Set Point C Temp Controller Reading Check Fault Buzzer Light Works Sight Glass Clear Unit Handles Heat Load On Off Button Works Check Oil level on the compressor sight glass Op...

Page 35: ...es and screws Commissioning by Inspected by Company Contact number Installation site Business name of site Site contact name Site contact phone no Sit contact position Note regarding to refrigeration...

Page 36: ...User Manual Thermal X R Series Chillers Page 36 Agent signature Date Customer representative print name Customer representative signature Filing Aqua Cooler Date Print name Signature NOTES...

Reviews: