User Manual Thermal X - R Series Chillers   

 

 

 

 

 

Page 25 

TROUBLESHOOTING 

In the event the chiller develops a fault then the fault is displayed on the screen readout on the control 
board. The faults displayed are comprehensive but not fully descriptive.

 

Symptom 

Possible Causes  Solutions 

L

o

F

lo

Ala

rm

 

Faulty Pump 

Replace Pump ensuring new pump has been leak tested, phase wiring is around 
the right way 

Blockage on 
water circuit of 
chiller 
installation 

Check water flow is coming back through to chiller. Water line isn’t isolated 
down the line. Water strainer is clean and clear (if installed in water pipe work.  If 
plate pack evaporator is used check there is flow through the heat exchanger. If 
blocked replace heat exchanger. 
Faulty electrical contractors – check operation and replace if necessary 

Work Around 

Set water flow alarm and protection to 0 while you test unit. (if unit has plate 
pack isolate compressors while testing) 

Faulty Flow 
meter 

Check flow meter spindle if free and not stuck, flow meter has voltage (24vdc) 
wiring connections are not loose. By-pass is not fully open. 

Co

mp

re

ss

o

F

a

ult

 

High head 
pressure – HP 
alarm tripping 

Check head pressures when the unit is running. Possible causes blocked 
condenser – check for dust or debris build up and clean.  Refer to “Poor Heat 
Dissipation” section. 
Dead or dying fan – check amp draw of fans or air flow. Replace if needed 
Too high a heat load for the rating of the unit. Check install and site 
specifications 
Bad installation or too high ambient – check that there is no other equipment in 
the vicinity that may be throwing heat onto the unit or that the unit has not been 
installed improperly 
Faulty HP transducer or HP switch - replace 

Low pressure – 
LP alarm 
tripping 

Flow rate from pump may be too low 
TX valve may have seized 
Unit may have developed a refrigeration leak and lost gas charge – check 
pressures or run leak detector over the unit. 
Outlet water temperature and evaporator temperature too low.  Check whether 
there is a lack of water in the water tank and whether the circulating pump is 
running well. If those are normal, reset the low pressure switch or restart the unit. 
If the evaporator is frozen, input warm water to melt the ice. Do not attempt to 
break the ice off with force. 

Work Around 

Motor protection module in compressor tripped 
Motor running too hot – return water may be too high in-rush of heat load. 
Compressor drawing too much current 

Multi 
compressors 

For multiple compressor units, Second compressor should still be running and 
carrying much of the heat load. Once the faulty compressor is fixed then the 
programming will have to be updated as the program will have defaulted to 
another setting to keep the unit running. 
On the screen go to “PARAMETERS MENU” and press “OK” 
Scroll to SWITCH ON FOR NEXT C” – “TIMER” should be showing 
underneath this. Press “OK” and scroll to “FIXED HEAT LOAD” and press 
“OK”. The screen should confirm your choice 

No

 P

o

wer

 

Main breaker 
off 

Check main breaker is on, If on and no power have a qualified person test power 
to the unit. 

P

CB

 

bla

nk

 

No mains power 

Check main breaker is on, If on and no power have a qualified person test power 
to the unit 

No control 
voltage 

Check PCB has 24vdc to controller. If power is present replace PCB 

Summary of Contents for Thermal X R Series

Page 1: ...s Page 1 Revision 2 AUGUST 2019 Thermal X R Series Owner s Manual This guide applies to the following models R150 to R4000 Aqua Cooler Pty Ltd U14 2 12 Knobel Court Shailer Park 4128 Qld www aquacoole...

Page 2: ...ng Sequence 9 Operating Precautions 9 CHLF2 60 10 CHLF4 60 10 CHLF12 40 11 CDMF20 4 11 CDMF32 30 12 Aqua Cooler Controller 12 Unlocking the Keypad on the Aqua Cooler Controller 12 Operational Logic of...

Page 3: ...chematic 24 Poor Heat Dissipation 26 Low Refrigerant 26 Low and High Pressure Difference 27 Compressor Not Starting 27 Maintenance 27 Recommended Preventative Maintenance Program 28 Warranty 28 Genera...

Page 4: ...process cool They are supplied with an immersed coiled evaporator or plate heat exchanger or shell tube evaporator model dependant an air cooled condenser and a rotary or scroll compressor to circula...

Page 5: ...ould be secured to prevent it from toppling over Minimum temperature setting is 5 C on the unit Any lower than this may cause problems with the evaporator icing up and potentially loss of refrigerant...

Page 6: ...possible If the unit is to be stored before installation then care must be taken to ensure no foreign matter can get into the water pipes If the storage is for a prolonged period it is recommended tha...

Page 7: ...ort the chiller s full operating weight Installation of the Water Path Before connecting the make up water check the suction pressure on in the chiller to ensure there is no refrigerant leak A refrige...

Page 8: ...ltage at the chiller under all load conditions Three phase power must be symmetrical ensuring equal effective voltage and equal phase angle between consecutive phases The pump and the compressor rely...

Page 9: ...oints and operational parameters are displayed on the screen Any faults are indicated on the face of the control panel It is a good idea after the unit has been running for 5 minutes check that the wa...

Page 10: ...R230 R300 R330 CHLF2 60 R420 R540 R670 R830 R1000 R1200 R1330 CHLF4 60 R1500 R2000 R2500 CHLF12 40 R3000 CDMF20 4 R4000 CDMF32 30 CHLF2 60 Model Driving Motor Q 3 0 5 1 0 1 5 2 0 2 5 3 0 3 5 CHLF2 60...

Page 11: ...12 40 Model Driving Motor Q 3 7 8 9 10 11 12 13 14 15 16 CHLF12 40 2 4 3 3 H 47 46 45 43 5 41 5 39 5 37 5 35 31 5 27 5 CDMF20 4 Model Driving Motor Q 3 0 10 12 14 16 18 20 22 24 26 28 29 CHLF12 40 5 5...

Page 12: ...7 AQUA COOLER CONTROLLER The chiller unit features an interface panel with LCD display and input buttons to configure certain functions of the unit Unlocking the Keypad on the Aqua Cooler Controller T...

Page 13: ...eratures too high or too low Temperature Control High and Low Temperature Alarm Stop High and low temperature limits can be set in order that if they are breached then the chiller will shut down In ra...

Page 14: ...et to run if the chiller develops a fault by turning this feature ON in the program will keep water to the process This water will of course get warm but it is designed to keep the process cool long e...

Page 15: ...the set point is 10 C the hystersis 2 C and the close tolerance 1 C then the controller will attempt to keep the temperature between 10 5 C and 11 5 C The ability of the chiller to keep the temperatur...

Page 16: ...ER TEMP will show Press the escape key to revert to home page Temperature Hysteresis Temperature between refrigeration circuits cut out and cut in Scroll to the PARAMETERS MENU then to the SET POINTS...

Page 17: ...by pressing the OK button Range Low 5 C to 10 C High 10 C to 40 C Scroll to PARAMETER MENU and to the SET POINTS sub menu Scroll to HIGH TEMP ALARM and LOW TEMP ALARM and press OK SET HI TEMP ALARM wi...

Page 18: ...nded that the setting is not greater than 1 or 2 minutes Tandem Installation Assigning the chillers into a single or tandem set installation Scroll to PARAMETER MENU and then to the SYSTEM sub menu Sc...

Page 19: ...allation YES on master chiller in N 1 installation VAR SPEED FUNCTION OFF On for chillers fitting with VFD on compressor or the pump NO HE SENSORS 0 LOW TEMP STOP YES AUX INPUTS N O FAN SPEED CONTROL...

Page 20: ...RM 1 0 1 L s MAX TEMP LIMIT 20 SUPPLY FLOW WARNING 1 Varies with pump supplied SET PT AMB OTEMP 45 SET POINT TEMP Customer Specific SENSOR MENU CCT1 SUCT PR SIZE 0 10 Bar SECONDARY SUPPLY CAL See Proc...

Page 21: ...vice Number 2012 ModBus RTU Slave Addr 1 247 head in the Chiller ID tab Again use the save password aquacustomer as the password 7 Then edit the page to the new IP address details for the chiller agai...

Page 22: ...e approximately 3 weeks of data logging 10 second intervals will only give 24 hours of data logging and the logging drops the old files off the end so if the unit has a problem and it takes more than...

Page 23: ...ted to the internet or to a BMS system the BIN file will need to be updated as well to the corresponding issue number Using a laptop connect to the Aqua Cooler controller via the Ethernet card in the...

Page 24: ...oss the bottom of the board IN1 NOT USED IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 Not Used 0 10V Input 0 10V NC Input 0 10V NC Input 0 10V NTC thermistor 0 10V NTC thermistor 0 10V NTC thermistor 0 10...

Page 25: ...no other equipment in the vicinity that may be throwing heat onto the unit or that the unit has not been installed improperly Faulty HP transducer or HP switch replace Low pressure LP alarm tripping F...

Page 26: ...ck operation of transducer reading correctly Low refrigerant charge Check refrigerant system operation check super heat and sub cooling are with in normal operating ranges High Ambient Temp Faulty pro...

Page 27: ...pressure switch is damaged 5 The overload protector of the compressor is damaged 6 The electromagnetic relay is damaged or the overload protector is damaged 7 The water level is too low 8 The refrige...

Page 28: ...be excluded under Australian Consumer Law You are entitled to replacement or refund for a major failure and to compensation for other reasonably foreseeable loss or damage You are also entitled to ha...

Page 29: ...User Manual Thermal X R Series Chillers Page 29 Installation Sketch Map of Air Cooled Chiller...

Page 30: ...User Manual Thermal X R Series Chillers Page 30 Installation Sketch Map of Water Cooled Chiller...

Page 31: ...User Manual Thermal X R Series Chillers Page 31 Internal Structure Sketch Map of Air Cooled Chiller...

Page 32: ...User Manual Thermal X R Series Chillers Page 32 Internal Structure Sketch Map of Water Cooled Chiller...

Page 33: ...of the completed table and send it back to us Customer and On Site Requirement Required Capacity kW Rated Ambient Temp C Rated Supply Temp C Rated Flow Rate L s Customer Address Machine Information C...

Page 34: ...NO Ambient Temp C Water Set Point C Temp Controller Reading Check Fault Buzzer Light Works Sight Glass Clear Unit Handles Heat Load On Off Button Works Check Oil level on the compressor sight glass Op...

Page 35: ...es and screws Commissioning by Inspected by Company Contact number Installation site Business name of site Site contact name Site contact phone no Sit contact position Note regarding to refrigeration...

Page 36: ...User Manual Thermal X R Series Chillers Page 36 Agent signature Date Customer representative print name Customer representative signature Filing Aqua Cooler Date Print name Signature NOTES...

Reviews: