9
quartz sleeve installation
The quartz sleeves designed for this unit are open
on both ends. For first time unit installations, follow
these quartz sleeve installation procedures:
1. Turn off all power to the unit.
2. Wear clean cotton gloves to prevent contamination
of the quartz sleeves.
3. Carefully remove the quartz sleeve from the factory
packaging. Handle with care as they are fragile.
4. Visually inspect all quartz sleeve(s) for cracks or
other damage. Do not install damaged quartz
sleeve(s).
5. Remove the covers from the treatment chamber.
6. Remove all compression nuts and any packaging
material from the end plate (if installed).
7. Place the end of the quartz sleeve into the threaded
nipple and slowly push the sleeve into the chamber
through to the second end plate.
8. Install the compression nut and o-ring by placing
the o-ring into the internal relief of the compression
nut below the threaded area. The o-ring should fit
into the compression nut.
9. Place the compression nut and o-ring onto the end
of the quartz sleeve. Allow the quartz sleeve to
extend an equal distance on both ends. Some
pushing and twisting may be required. Deionized
water may be used as a lubricant.
10. Tighten the compression nut approximately 1/2 turn
after the threaded nipple and o-ring make contact.
11. Repeat this procedure for the second endplate.
12. Slowly pressurize the system and fill the chamber
with water to check for leaks.
13. If the compression nut leaks, use the special tool to
screw the compression nut assembly onto the
threaded nipple. Do not exceed 40 inch-pounds of
torque.
14. You are now ready to install the UV lamp(s).
Over tightening
can break the
quartz sleeves
or create leaks.
Remove unit cover.
Insert quartz sleeve into threaded nipple.
Socket retainer cap on comp nut
Rotate compression nut clockwise