PARAMETERS
There are 10 variable parameters (0 – 9) which can be set. There are 5
fixed parameters (A – E) which are for information only.
Parameter 4
Defrost exit temperature.
Defrosting function (0 –
30˚C). Default setting:
13˚C.
Parameter 5
Maximum time of
defrosting (0 –
15min). Default
setting: 8 min.
Parameter 2
Heating time when
in defrost mode
Parameter 1
To set the inlet water
temperature when in
heating mode (15 – 40˚C).
Default setting: 27˚C
Parameter 6
System Quantity
(don’t set).
Parameter 7
Automatic restarting
0 – No
1 – Yes
Parameter 8
Mode:
0 (cooling only)
1 (cooling & heating)
2 (auxiliary elec. heating)
3 (heating only)
Parameter 0
To set the inlet water
temperature when in
cooling mode (8 – 28˚C).
Default setting: 27˚C.
Parameter 3
Defrost starting
temperature. Defrosting
function (-30 – 0˚C).
Default setting: -6˚C.
5
Parameter 9
Pump:
0 (always open)
1 (10 sec. start before compressor
starts. 30 sec. stop after
compressor stops)
Inlet water
temperature
HOW TO SET THE PARAMETERS
The machine must be in the “OFF” position.
Press or to scroll until you reach the required parameter.
Press “MODE” and “ON/OFF” switch simultaneously and release. (NB
quick press and release!).
The parameter value will start flashing. Use the or to change the
value to the required setting. Wait until the LED has reverted back to time.
A new parameter setting is programmed.
Press to restart the machine.
Outlet water
temperature
Condenser 1
temperature
Condenser 2
temperature
Ambient
temperature
6