background image

Digit

Meaning

Range

Default Adjust 

(yes/no)

0

Inlet water temperature when in cooling 

mode

8 - 28°C

27°C

Yes

1

Inlet water temperature when in heating 

mode

15 - 40°C

27°C

Yes

2

Heating time when in defrost mode

30 – 90 Min 45 Min

Yes

*3

Defrosting start temperature

0 – 30°C

-6°C

Yes

4

Time of exiting defrost mode to temperature

0 - 30°c

13°c

Yes

5

Time of exiting defrost mode to heating 

mode

1 – 12 Min

8 Min

Yes

6

System quantity

1 – 2

2

Yes

7

Automatic restarting after power failure / 

disconnection

0 (no)

 1 (yes)

1

Yes

8

Mode:  

cooling only

cooling / heating 

auxiliary electrical heating

heating

0

1

2

3

3

Yes

*9

Pool pump supply from heat pump “1”

Pool pump supply from the remote supply / 

DB “0”

0/1

1

Yes

OPERATIONAL STATUS

Notice:  Above data setting “0” is relevant to cooling mode only.  All other 

data, (i.e. 1 – 8) is relevant to heating.
*Remark:
Parameter 3:
  0-30°C means from (-30°) to (0°)
  6°C means -6°C
Parameter 9:
  0:    always open
  1:    The pool pump will start 10 seconds before compressor has started
           The pool pump will stop 30 seconds after the compressor has stopped

7

LED

Controller

Malfunction

Reason

Solution

PP1

Water inlet temp. sensor 

failure

The sensor doesn’t detect 

a reading

Switch power supply off 

for 5 minutes, then switch 

on again

PP2

Water outlet temp sensor 

failure

The sensor is open or 

short circuit

Check or change the 

sensor

PP3

Coil 1 sensor failure (C)

The sensor is open or 

short circuit

Check or change the 

sensor

PP4

Coil 2 sensor failure (D)

The sensor is open or 

short circuit

Check or change the 

sensor

 PP5

Ambient temperature 

sensor failure (E)

The sensor is open or 

short circuit

Check or change the 

sensor

PP6

Temp differential between 

water-in and water-out is 

too high

Water flow volume too low, 

water pressure difference 

is too low

Check the water flow 

volume/pressure

PP7

Machine in defrost mode

Ambient or inlet water 

temp is very low

Wait for machine to return 

to heating mode

EE1

Malfunction of system 1

System 1 protection has 

failed

Switch power supply 

off for 5 minutes, then 

switch on again.If failure 

continues, call agent

EE2

Malfunction of system 2

System 2 protection has 

failed

Switch power supply 

off for 5 minutes, then 

switch on again.  If failure 

continues, call agent.

EE3

Flow switch failure

No water flow/insufficient 

water in water system

Check the water flow 

volume, replace water flow 

stitch 

EE4

Power supply connections 

wrong 

(for TF 100/3 and 130/3)

Wrong connections or lack 

of connection

Check connection of 

power supply

No display

Power supply connections 

wrong

 (for SF060/3, 080/3, 

130/3, 200/3)

Wrong connection or lack 

of connection

Check for gas leaks and 

check pressure switches

EE4

Overheating of 

compressor/system 

(for 

SF012/015/020/030/050 & 060/3)

Gas charge too low or high.  

Possible system blockage

Check for gas leaks and 

check pressure switches

EE5

Difference between inlet 

water temperature and 

outlet water temperature 

too high

Water flow rate too low or 

no water

Check the water flow rate 

and repair

EE8

Communication failure

LED and PLC connection 

failure

Check wiring

TROUBLE SHOOTING GUIDE

8

Summary of Contents for Keypad

Page 1: ...ature you can only view the settings In order to change the settings the machine must be in the OFF position i e showing time The rate of heating the water will be the same it does not matter what the required set temperature is i e by setting the temperature very high this won t increase the rate of heating By setting the required temperature too high this will only cause a higher electricity con...

Page 2: ... will flash Use the or to set the required minutes Once the minutes have been set press TIMER ON again to save the time setting 3 How to Set The Timer OFF time when machine need to run in 24 hour cycle Whilst the machine is in the OFF position i e showing time press TIMER OFF twice The first two digits on the LED screen will flash Use the or to set the required hours Press TIMER OFF again The last...

Page 3: ...To set the inlet water temperature when in cooling mode 8 28 C Default setting 27 C Parameter 3 Defrost starting temperature Defrosting function 30 0 C Default setting 6 C 5 Parameter 9 Pump 0 always open 1 10 sec start before compressor starts 30 sec stop after compressor stops Inlet water temperature HOW TO SET THE PARAMETERS The machine must be in the OFF position Press or to scroll until you r...

Page 4: ... Coil 2 sensor failure D The sensor is open or short circuit Check or change the sensor PP5 Ambient temperature sensor failure E The sensor is open or short circuit Check or change the sensor PP6 Temp differential between water in and water out is too high Water flow volume too low water pressure difference is too low Check the water flow volume pressure PP7 Machine in defrost mode Ambient or inle...

Page 5: ... blanket you will not be able to maintain a constant temperature in your swimming pool A good example to think of is driving your car with the air conditioning on and all the windows down WHY IS THERE WATER DRIPPING FROM UNDER THE HEAT PUMP When the heat pump is running in the heating mode condensation build up on the evaporating coils will cause water dripping under the heat pump This is a normal...