background image

9

0-10V Information

Please read and understand the following information about 0-10V Wiring:

• Local site wiring must utilize properly rated insulation so no spacing or separation is required regardless of circuit 

conductor voltage.

• The local site must utilize power limited/circuit wiring that has the required insulation rating for the maximum voltage in 

any of the circuits if the power limit/branch circuit wiring comes in contact with other wiring.

• Class 2 0-10V Wiring follows NEC Requirement 725.136 (D). Meaning electric light, power, and Class 1 circuits must 

have a 6 mm separation from the Class 2 Wiring.

• Conductors that operate at 150V, or less, to Ground must comply with the following: 

The Class 2 circuits are installed using Type CL3, CL3R, or CL3P or permitted substitute cables provided these Class 
3 cable conductors extending beyond the jacket are separated by a minimum of 6 mm (0.25 in.) or by a non-
conductive sleeve or non-conductive barrier from all other conductors.

 

• There must be a minimum of 0.25 in. between line voltage and bus terminals for Class 2 installations.

TROUBLESHOOTING/CORRECTIVE ACTIONS

Troubleshooting/Corrective Action Assessments can only be performed by qualified/trained personnel. Failure to do so will void 
any Aquarii Product Warranties.

If the Zino is still not functioning as required after the Troubleshooting/Corrective Actions have been performed, please contact 
Aquarii Customer Service for further assistance.

SYMPTOM

POSSIBLE CAUSE

CORRECTIVE ACTION

No light output

Power is off

Check if power supply is on

Poor wire connection

Check wiring connections

Faulty supply switch

Test or replace supply switch

Shorted dim lines

Verify no shorts in dim lines

Fuse blown or Circuit Breaker trips

Crossed wire(s) or a supply 

wire has grounded out

Check wiring connections

Red LED diode illuminated on 

Controller

Faulty Communication

Verify Correct Communication 

Protocol

Red + Green LED diode illuminated 

on Controller

Faulty Controller

Replace the Controller

Green LED diode not illuminated on 

Power Supply

Faulty Power Supply

Replace Power Supply

Local Site Power issue

Verify local site Power Supply is 

on/running

Summary of Contents for RHEOS

Page 1: ...P N 30 00302 ZINO Slope Recessed Installation Manual DO NOT DISCARD THIS MANUAL ...

Page 2: ...gs 1 Aquarii Warranty 1 Schedule A 3 Aquarii Product Return Policy 3 Mounting Option 4 Slope Recessed 4 Wiring Connections 5 Secure Power Connections 5 Communication Connections 6 Secure DMX RDM Connection 6 DMX Addressing Information 7 DMX over CAT5e 6 7 Secure 0 10V Connection 8 0 10V Information 9 Troubleshooting Corrective Actions 9 ...

Page 3: ...y installation or mounting procedures Do not connect the fixture to an electrical system that does not provide grounding equipment Do not connect the fixture to a power source with a Voltage AC level outside the fixture parameters The fixture cannot be hung with supply wires or wire connectors Wiring MUST NOT come into contact with any surfaces that have sharp edges to ensure personal product safe...

Page 4: ...ive of Seller improper or unauthorized use installation handling storage alteration maintenance or service including failure to abide by any product classifications or certifications or failure to comply with any applicable standards codes recommendations product specification sheets or instructions of Seller use of the Product with products processes or materials supplied by any end user or third...

Page 5: ...e to receive a RMA Number for your return Product s returned without a RMA will delay or may void any return credit 2 Clearly note the RMA Number on the shipping container and packing slip 3 Please return all product s as freight prepaid unless instructed otherwise by customer service 4 Include all paperwork provided by Aquarii such as the Warranty Claim 5 Ship all returns to the following address...

Page 6: ...eters based on the present building material 3 Loosen the Adjustment Nuts to adjust the orientation of the fixture inside the Box Assembly then tighten the Adjustment Nuts to secure the fixture in the desired orientation 4 If a Trim Ring is required proceed to Step 5 if not then Proceed to the Wiring Connections section of this manual 5 Obtain the Trim Ring Springs from the separate packaging acco...

Page 7: ...ds of the Power Cable in the Wagos connected to the Ground Strap and Power Supply Wire Connections Site Ground Wire Ground Strap in Junction Box Site Neutral Wire Blue Lead of Power Supply Wire Connection Site Line Voltage Wire Brown Lead of Power Supply Wire Connection 3 Reinstall the Junction Box Cover 4 If additional Communication Wiring is required proceed to the corresponding section starting...

Page 8: ...0005 RJ 45 P N 17 00004 Insulation Displacement Connector IDC P N 17 00003 Screw Terminal P N 17 00002 2 Ensure the DMX Wire Harness connection from the Controller to Communication Board has not been disrupted 3 Set the fixtures DMX Address as needed NOTE All DMX Wiring should be compatible with Telecommunications Industry Association TIA EIA 485 RS 485 See the table on Page 7 of this manual for t...

Page 9: ...ay use these wires for this purpose Because of these various uses mis plugging unlike systems could cause serious damage DMX Addressing Information The Zino LED Fixture requires one DMX Channel in a universe See the example below for how to address the fixture Channel 1 Intensity 0 255 An intensity value of 0 will cause the fixture to not illuminate while a value of 255 is the highest intensity Se...

Page 10: ... 0 10V Communication Wiring to the fixture 1 Ensure the local sites power supply is shut off for personal safety 2 Determine the type of circuit present at the local site 3 Secure the Screw Terminal Plug in Connection from the local site to the 0 10V Communication Board 4 Confirm the Polarity for 0 10V Communication Wiring 5 Test the fixture to ensure proper function 108 3 30 6 7 8 5 3 6 5 0 09 6 ...

Page 11: ...ctors There must be a minimum of 0 25 in between line voltage and bus terminals for Class 2 installations TROUBLESHOOTING CORRECTIVE ACTIONS Troubleshooting Corrective Action Assessments can only be performed by qualified trained personnel Failure to do so will void any Aquarii Product Warranties If the Zino is still not functioning as required after the Troubleshooting Corrective Actions have bee...

Reviews: