AT-G-DETECT

Gas Sensing System

LEAK DETECTION SOLUTIONS

4

8. Tighten on the ampoule until it shatters

allowing the content to di

 use in the

beaker. It should be left in place for
approximately 5 min.

9. Voltage output will increase. This con

fi

 rms

that the sensor is responding. In the case
of ampoules a response equivalent to 50%

F. BUMP TEST USING GAS AMPOULES

or greater of the ampoule concentration 
will be satisfactory.

10. Carefully remove any ampoule remains

from the gas detector, replace yellow cap
(only CO2 sensors), and replace the sensor
enclosure.

Remove the enclosure lid of the gas sensor and controller (non applicable to Exd Remote 
sensor and vent pipe model, 1L units as monitoring of voltage can be done on controller) if 
this is a CO2 unit also remove the yellow cap on the calibration port, if on your model.Connect 
the voltmeter to the controller to monitor sensor response. Expose the sensor to gas from the 
cylinder. You can place the entire sensor into a plastic bag or use a plastic hose/hood to direct 
gas to the sensor head.

G. CALIBRATION

The alternatives we describe are:
• Exchanging the sensor board – only

available for 2 level units

• Gas Calibration

H. EXCHANGING THE SENSOR BOARD

Aquilar recommends exchanging your PCB for a newly pre-calibrated certi

fi

 ed unit every 3 years

TOOLS REQUIRED

•  A pre-calibrated sensor board
• A voltmeter – crocodile clips recommended
• Estimate 10 min per sensor

EXCHANGINF THE SENSOR

1. Power o

  the unit and remove lid of

sensor enclosure.

2. Note the colour code of the cable in

positions 1,2,3,and 4 of the connector 
block.

3. Undo the cable and 2 screws securing

sensor board and remove.

4. Fit the new pre-calibrated sensor and

reconnect the cable in the correct colour
sequence at positions 1,2,3 and 4.

Unit 30, Lawson Hunt Industrial Park, 

Broadbridge Heath, Horsham, West Sussex, 

RH12 3JR
+44 (0) 1403 216100
info@aquilar.co.uk
www.aquilar.co.uk

Summary of Contents for AquiTron AT-G-DETECT

Page 1: ...AT G DETECT Refrigerant Gas Sensing System Check Calibration Procedure AquiTron CA L I B R AT I O N P R O C E D U R E...

Page 2: ...ective is to establish if the sensor is reacting to the gas and all the sensor outputs are working correctly A quantified bump test is one where gas of a know concentration is used CALIBRATION This co...

Page 3: ...r does not go into alarm carry out a gas calibration If the factory set point information is not on the calibration label as with older units check the serial number of your gas detector on the rating...

Page 4: ...OULES 1 Make sure that both the ampoules and the calibration beaker are clean and dry 2 Unscrew the beaker hold screw and place the ampoule so that it sits in the base of the beaker 3 Tighten on the s...

Page 5: ...o the controller to monitor sensor response Expose the sensor to gas from the cylinder You can place the entire sensor into a plastic bag or use a plastic hose hood to direct gas to the sensor head G...

Page 6: ...3 minute alarm delay on a one level system by moving the jumper link at JP1 to the o position Two adjustments are required and they are all performed on the controller unit A Sensor Standby Voltage S...

Page 7: ...used drift B Alarm Threshold Voltage ATV Low Treshhold Connect voltmeter between TP5 0V TP2 Ve set the voltage asshown on the calibration label by adjusting pot P8 High Threshold Connect voltmeter bet...

Page 8: ...r extreme humidity or temperature conditions you may adjust the settings to compensate One Level Systems You should reduce the SSV level in 0 5V increments until the condition clears Two Level Systems...

Page 9: ...libration label You can monitor this as follows 1 level systems Connect a Voltmeter and monitor voltage between Pins 4 Ve 2 Ve of the sensor terminal connector block for each channel in turn CN1 CN2 E...

Reviews: