background image

SENSOR

RED

GRN

YEL

BLK

x3
x7
x10
x12

Figure 7

AT-MZA

 

Multi Zone Alarm

LEAK DETECTION SOLUTIONS

Weights & Measures House, 20 Barttelot Road, 
Horsham, West Sussex RH12 1DQ

+44 (0) 1403 216100

info@aquilar.co.uk

www.aquilar.co.uk

5

CONNECTING THE POWER WIRING

• Open door of MZA enclosure.
• Pass the power cable through the knock- 

  out/adapter/bushing if fitted.

• Note:

 Proper grounding/earthing is  

important to avoid the possibility of     
electromagnetic interference.

• Connect the power supply wires to the  

special three-pin terminal block marked LNE 
(Live, Neutral, Earth), observing the polarity.

E. CONNECTING THE POWER CABLE AND RELAYS

x15

Figure 4

L

 

N

• The electrical supply should be fused 

at no more than 3 amps via an un-
switched fused spur adjacent to the 
unit. 

• Note:

 Do not exceed maximum 

voltage.

• The unit is equipped with a 12Vdc battery 

back-up power circuit. If this option is 
required connect the + and - (positive and 
negative) battery leads (leads not supplied) 

(fig 7).

BATTERY BACKUP

Figure 5

• A separate battery unit is available 

AT-BU which will house a 12Vdc 7Ah 
battery - AT-BAT.

• Batteries should be tested, maintained 

and replaced in accordance with the 
battery manufacturers instructions 
and recommendations.

COCONNECT THE LEAK AND FAULT 

(CABLE BREAK) RELAYS

The MZA has:

 

One LEAK relay per zone 
One common LEAK relay 
One summary FAULT relay

RELAY IDENTIFICATION

LEAK relays:

Zones1&2,X13-Z1bottom,Z2top 
Zones3&4,X11-Z3bottom,Z4top 
Zones5&6,X8-Z5bottom,Z6top 
Zone7&8,X5 -Z7bottom,Z8top

Note:

 See figure 8 (at the back of this 

document) for a complete figure layout. 

Figure 5

Figure 6

Figure 7

Summary of Contents for AquiTron AT-MZA

Page 1: ...AT MZA Multi Zone Alarm AquiTron INSTALLATION INSTRUCTIONS...

Page 2: ...n Class I Division 2 Groups A B C D Hazardous Locations If protected by agency approved zener barrier TraceTek sensing cable in Class I Division 1 Groups A B C D Hazardous Locations Zone 0 or Zone 1 i...

Page 3: ...14 Z1 2 Leak relay cable plug and socket 15 Z1 2 Sensing cable plug and socket 16 Z3 4 Leak relay cable plug and socket 17 Z3 4 Se nsing cable plug and socket 18 Z5 6 Leak relay cable plug and socket...

Page 4: ...sure to static electricity Avoid contamination with metal filings liquids or other foreign matter Remove the module from its packaging Open the enclosure door using a flat blade screwdriver or coin An...

Page 5: ...ur coded wires to the Sensor Interface plug X3 X7 X10 and X12 see Fig 4 SENSOR RED GR N YEL BLK x3 x7 x10 x12 Select a spare connector between zones 1 to 8 Zones 1 2 do not require the insertion of a...

Page 6: ...an 3 amps via an un switched fused spur adjacent to the unit Note Do not exceed maximum voltage The unit is equipped with a 12Vdc battery back up power circuit If this option is required connect the a...

Page 7: ...nical damage Keep the electronics dry If handling circuit boards hold them by their edges to avoid physical contact with electronic components Avoid exposure to static electricity Avoid contamination...

Page 8: ...terminals So to operate a valve for example you need to have a dedicated power supply which is then fed through the relay typically the live feed to switch it on or off accordingly Typical wiring is a...

Page 9: ...a plan showing the location of the sensor is available 3 Check that the following information is clearly visible adjacent to the alarm module In case of alarm instruction Location of the system map in...

Page 10: ...portion of the system to verify circuit integrity to detect the presence of liquid and even to determine its location as the PTB will give you an indication in feet or metres to the point of the leak...

Page 11: ...older or weld near the cable without providing protection from heat solder flux or weld splatter Do not drop tools or floor tiles on the cable sharp and heavy objects may damage the cable Avoid walkin...

Page 12: ...ssary or insert a small piece of insulating material to prevent the cable from making contact with the metal edge Problem Leak Alarm but no leak is found Possible Cause Cable is pinched all cables Act...

Page 13: ...nvestigate the cause of the spill and take necessary repair actions 2 Clean up in the spill area and clean and dry the cable probe if necessary LEAK LED will turn off when cable probe is dried CABLE B...

Page 14: ...ar co uk 13 FIG 8 TERMINAL CONNECTION LAYOUT SENSO R RED GR N YEL BL K Z8 x3 Z7 N O CO M N C LEAK REL AY x5 SENSO R RED GR N YEL BL K Z6 x7 Z5 SENSO R RED GR N YEL BL K Z4 x10 Z3 SENSOR RED GR N YEL B...

Page 15: ...be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notice In addition Aquilar Limite...

Reviews: