proper operation.

The  OPSEN  optical  sensor  has  been
specifically  designed  for  use  with  TraceTek
and AquiTron™ leak  detection systems.

The  OPSEN  is  designed  for  use  in  ordinary
areas with temperatures of 0°C to 50°C (32°F
to 122°F).

Zones / Regions

Probes  with  terminal  strips  and  built  in
resistors (weighted lengths) equal to 8 metres
(25  feet)  for  the  first  sensor  and  16  metres
(50  feet)  for  each  subsequent  sensor  when
used on the TraceTek TTDM or TTSIM-1/1A/2
alarm & locator panels.

If sensors are used alone on a circuit, without
sensing cable, the ‘zones’ setting within ‘units’
can be used on the panels.

Power Supply

Each OPSEN requires a 12Vdc power supply. Power is available from
a separate power supply unit: AT-PSU-1 for 1 to 10 sensors.

The 12Vdc should be connected as detailed below, care should be
taken when connecting the power as the sensor is polarity sensitive.

The  Bulk  OPSEN  cable  is  colour  coded  for  connection  into  the
TraceTek and AquiTron™ panels: white 12Vdc (+) and blue OV (-)
should be used for the power cables.

Power indication 

The  sensor  unit  is  provided  with  a  GREEN  LED  to  indicate  power
present.

Alarm indication

In  the  event  of  a  leak  being  detected  the  units  RED  LED  will
illuminate.

Indication  will  also  be  displayed  on  the  following  leak  detection
panels:
AT-SZA, single zone indication.
AT-DIM, single zone indication.
AT-MZA, individual zone indication.
TTDM, distance or zone number/region/area name.
TTSIM-1/1A/2,  via  the  master  panel  or  BMS  a  distance  or  zone
number/region/area name is available.

Detection time

The Optical sensor head will detect the presence of a liquid within
seconds of it making contact. The alarm activation on the OPSEN
(Red LED) will be immediate, however, alarm indication on the leak
detection control panel will depend on the model selected. 

Application Liquids

The  OPSEN  has  been  designed  for  use  with  hydrocarbon  based
liquids such as fuels and oils. The sensor will also detect other none
aggressive liquids. 

The  OPSEN  optical  sensor  head  will  also  detect  water  and  many
other chemicals.

For further liquids please contact your distributor.

Maximum number of Sensors

TTDM and TTSIM panels - 100
AT-SZA, AT-DIM and TTSIM-1A - 10
AT-MZA - 10 per channel/zone

Temperature 

Environment:

Storage: -18°C to 60°C (0°F to 140°F) 
Operating: 0°C to 50°C (32°F to 122°F)

Liquid:  

Operating: 0°C to 50°C (32°F to 122°F)

Enclosure:

IP67

Tools required

Phillips (cross-head) screwdriver
Small flat-head screwdriver

Storage

Keep the module in a dry place prior to installation to avoid possible
damage to internal components.

Additional items

AT-PSU - 1

OPSEN Power Supply Unit (max 10 sensors)

AT-OPSEN-CBL  Bulk OPSEN Cable (50 metre reel)

aquilar

 -

 leak

 detection

 solutions

TraceTek or AquiTron™

Leak Detection Alarm Panel

AT-PSU-1

AT-OPSEN

Optical Oil Sensor

OPSEN Communications Cable

Reviews: