every second), Status (output on
change of Status) and Universal
Configurable Serial Time Code
RS-422/485
Transmit only, to drive multiple devices;
includes TxD-COM1, TxD-COM2, IRIG-B, Prog
Pulse A, Prog Pulse B, 1 PPS, Unlocked, Event In
6.4.3
Suggestions for Main Wiring
The standard sealing cable port is suitable for mounting cable with
an outer diameter ranging from 0.24 to 0.47 in (6 to 12 mm); choose
alternate sealing port with dimensions 0.20 to 0.35 in (5 mm to 9 mm).
Two Phoenix terminal blocks provide wire connections to the clock. This
section gives additional information on the sealing cable port and the
connector block.
Selected Connector Block Terminals Specifications
Screw thread
M 3
Tightening Torque
0.5 N m
Insulating Material Group
I
Rated surge voltage
4 kV (III/3, III/2, II/2)
Rated voltage
320 V (III/2), 640 V (II/2)
Connection STD
EN-VDE
Conductor, solid
0.14 mm to 2.5 mm (0.006 in to 0.098 in)
Conductor, stranded
0.14 mm to 1.5 mm (0.006 in to 0.059 in)
CSA
Nominal voltage, U
300 V
Nominal current, I
10 A
AWG/kcmil
28-14
CUL
Nominal voltage, U
300 V
Nominal current, I
10 A
AWG/kcmil
30-14
UL
Nominal voltage, U
300 V
Nominal current, I
10 A
AWG/kcmil
30-14
Certification
CB, CCA, CSA, CUL, GOST, SEV, UL
59