3. Input Type, Input Ratio or Phase Offset for “M-
type” CT SELECT values are protected from di-
rect change in the 928A.
4. If choosing a CT SELECT value of USER, you
can change any value in configuration screen.
5. When finished configuring, highlight
<
STOre
And Exit
>
and press
ENT
to exit this menu.
Low Range Mode
For current measurements below 10 mA rms (i.e. into
the 928A itself, not the CT) it may be advisable to
switch the Low Range Mode ON. The Low Range
Mode, multiplies the input signal by a factor of 20,
and can improve accuracy and stability of the signal.
Input signals above 10 mA rms may cause clipping.
Voltage Ch-B V
Change the Channel B voltage configuration in the
same manner as for Ch-A V as described above. Re-
member that these settings only apply for Channel B
when selecting the voltage function.
Current Ch-B I
Change the Channel B current configuration in the
same manner as for Ch-A I as described above. Re-
member that these settings only apply for Channel B
when selecting the current function.
Current Probe Configuration Examples
For secondary side measurements, you will need to set
up the instrument scale factors so that you can cor-