34
14. TROUBLESHOOTING
14.1. CONTROL PANEL “TERMODUE” – 2007 rel. TROUBLESHOOTING
Problem encountered
Solution
On the display appears the message:
"Disconnected or faulty probe, i.e. solar
panels probe, call for assistance”
The probe could be faulty or its circuit could be open (check for
an open in the wiring or replace the probe)
In some cases the value set by the parameter “Function
parameter #1” could be wrong; check again for a correct
parameter value.
The probe on the display shows (- - -)
instead of the normal value.
This is not an error because a disabled probe always shows - - -.
The boiler temperature does not rise and
the display shows “door open”
Check for a correct ajar switch connection as shown on the
electrical schematic diagram. If the message is still shown, check
for correct microswitch positioning with the door closed; if
necessary adjust the microswitch position.
The reading of one or more probes is
erratic.
Try to use a shielded cable for the probe connection to the board
to avoid electrical noise being collected by the cables. Refer to
paragraph 7.1.
For any kind of problem we recommend having the boiler inspected by technically skilled personnel or by an
authorized assistance center.