12
4.1 MINIMAL VALUE OF THE BURNER OUTPUT AT FIRST STAGE
If you have a two-stage burner, the first flame has to be set according to the values shown in the following table
in order to prevent boiler corrosion. The smoke temperature is not to be lower than 120°C.
MODEL
MIN. BURNER OUTPUT AT
FIRST STAGE kcal/h (kW)
MK 100
54'000 (63)
MK 120
64'000 (74)
MK 140
72'000 (83)
MK 170
88'000 (102)
MK 220
106'000 (123)
MK 280
132'000 (153)
PRK 320
160'000 (186)
PRK 400
225'000 (262)
PRK 500
275'000 (320)
PRK 600
335'000 (390)
PRK 740
412'000 (480)
PRK 830
464'000 (540)
PRK 1050
568'000 (660)
PRK 1200
653'000 (760)
PRK 1450
790'000 (920)
PRK 1850
1'005'000 (1170)
PRK 2350
1'280'000 (1490)
PRK 3000
1'548'000 (1800)
PRK 3500
1’800'000 (2100)
5. INSTALLATION
5.1 HYDRAULIC DIAGRAM
Legend:
C Boiler
PA Anti-condensation
pump
P
Air bleeding
PI
System pump
S
Safety valve
VE
Expansion vessel
VM
Mixing valve
GR
Water loading group
VR
Non-return valve
A
Hydraulic alimentation
M
System flow
D
Litre meter
R
System return