Cable length (min…max)
3…40 m
Cable diameter
1.0 mm
Detection radius
360º
Bending radius
5 cm
Operating temperature
–40…+85 ºC
AQ-07 fiber optic loop sensor
Material
Covered glass fiber
Light intensity threshold
8,000 lux
Cable length (min…max)
3…50 m
Cable diameter
1.2 mm
Detection radius
360º
Bending radius
1 cm
Operating temperature
–40…+85 ºC
AQ-08 fiber optic loop sensor
Material
Covered glass fiber
Light intensity threshold
8,000 lux
Cable length (min…max)
3…15 m
Cable diameter
1.2 mm
Detection radius
360º
Bending radius
1 cm
Operating temperature
–40…+125 ºC
10.6. Disturbance tests
Electromagentic compatibility test
CE-approved and tested according to EN 50081-2 and EN 50082-2
Emission
Conducted (EN 55011, class A)
0.15…30.00 Hz
Radiated (EN 55011, class A)
30…1,000 MHz
Immunity
Electrostatic discharge (IEC 244-22-2 and EN 61000-4-2, level 4)
Air discharge: 15 kV
Contact discharge: 8 kV
Electrical fast transients (EN 61000-4-4, class III & IEC 801-4, level 4)
Power supply input: 4 kV, 5/50 ns
Other inputs and outputs: 4 kV, 5/50 ns
Surge (EN 61000-4-5, level 4)
Between wires: 2 kV, 1.2/50 µs
Between wire and earth: 4 kV, 1.2/50 µs
RF electromagnetic field (EN 61000-4-3, level 3)
f = 80…1,000 MHz, 10 V/m
Conducted RF field (EN 61000-4-6, level 3)
f = 150 kHz…80 MHz, 10 V