14. If you are using the BI2 binary input as the master trip, activate it and verify that the trip has
occurred by repeating the steps 4 and 5.
15. Press the SET
SET push button to reset all indications and latches.
16. Repeat the steps 1 through 15 for all sensors.
8.3. Testing the CBFP function
The circuit breaker failure protection (CBFP) function is tested by taking the light signal and the
secondary trip criterion signal (if applicable) and leaving them active for longer than the set CBFP time
(that is, 100 or 150 ms). The T2 trip relay and the BO1 binary output must be active after the set time
delay has passed to confirm the CBFP function operates correctly.
8.4. Testing the unit operation time
An operation time test is not required at commissioning as it is performed by the manufacturer both as
a type test and as a routine production test. If you want to have more information of these tests, please
refer to the routine test reports sent with the AQ-102 unit and/or consult your nearest Arcteq
representative for the type test reports.
However, if it is deemed necessary, you can conduct an on-site timing test with the following
instructions.
1. Use a calibrated relay test set.
2. Connect one of the test set's outputs to a camera flash (Canon xxx or equivalent) to initialize
the flash and to configure the set's timer to start simultaneously with the flash.
3. Connect one of the AQ-102 unit's trip outputs (T1, T2, T3, T4) to a test set input and
configure the input to stop the timer.
4. Place the camera flash within 20 cm (12 inches) of the sensor.
5. Initiate the flash and the timer by using the test set output.
6. Read the measured time between the simulated arc light and the operation of the trip
contact.
7. Subtract the digital input delay of the test set from the final measured time (if applicable). For
specific test instructions, please consult the manufacturer of the relay test set.
8.5. Test plan example
A
AQ
Q-102L
-102LV
V
Version: 1.00
29
© Arcteq Relays Ltd
Summary of Contents for AQ-102LV
Page 1: ...AQ 102LV Arc flash protection unit ...
Page 24: ...7 Connections A AQ Q 102L 102LV V Version 1 00 23 Arcteq Relays Ltd ...
Page 25: ...Figure 7 10 Rear terminals of AQ 102LV A AQ Q 102L 102LV V Version 1 00 Arcteq Relays Ltd 24 ...
Page 26: ...A AQ Q 102L 102LV V Version 1 00 25 Arcteq Relays Ltd ...
Page 31: ...A AQ Q 102L 102LV V Version 1 00 Arcteq Relays Ltd 30 ...