10. Technical data
10.1. Protection
Trip time using mechanical trip relays
7 ms*
Reset time (arc light stage)
2 ms
*) The total trip time when using both the arc light (L>) or phase/residual overcurrent (I>) from an
AQ-110 unit and the arc light (L>) from this unit.
10.2. Outputs
10.2.1. Trip relays
Number of trip relays
4 NO or
or 3 NO + 1 NC
Voltage withstand
250 V AC/DC
Carry:
- continuous carry
- 3 s make and carry
- 0.5 s make and carry
5 A
16 A
30 A
Breaking capacity DC*
40 W (0.36 A at 110 V DC)
Contact material
AgNi 90/10
*) When the time constant L/R = 40 ms.
10.2.2. Binary output(s)
Rated voltage
+24 V DC
Rated current (max.)
20 mA
Number of outputs
1
10.2.3. System failure relay
Number of SF relays
1
Rated voltage
250 V AC/DC
Carry:
- continuous carry
- 3 s make and carry
- 0.5 s make and carry
5 A
16 A
30 A
Breaking capacity DC*
40 W (0.36 A at 110 V DC)
Contact material
AgNi 90/10
*) When the time constant L/R = 40 ms.
10.3. Binary inputs
Nominal threshold voltage
24 VDC
A
AQ
Q-102L
-102LV
V
Version: 1.00
© Arcteq Relays Ltd
32