Carry:
- continuous carry
- make and carry for 3 s
- make and carry for 0.5 s
5 A
16 A
30 A
Breaking capacity DC*
40 W (0.36 A at 110 V DC)
Contact material
AgNi 90/10
*) When the time constant L/R = 40 ms.
11.3. Binary inputs
Nominal threshold voltage
24 VDC
Threshold:
- pick-up
- drop-off
≥
15 VDC
≤
14 VDC
Rated current
3 mA
Number of inputs
2
11.4. Auxiliary voltage
Auxiliary power supply
92…265 V AC/DC
18…72 V DC (optional)
Maximum interruption
100 ms
Maximum power consumption
5 W, < 10 m
Ω
Standby current
90 mA
11.5. Sensors
AQ-01 point sensor
Light intensity threshold
8,000 lux
25,000 lux
50,000 lux
Detection radius
180º
Mechanical protection of the whole sensor
Mechanical protection for the active light detection part of the sensor
IP 20
IP 60
Sensor cable specification
Shielded twisted pair 0.75 mm
2
(AWG: 20)
Maximum sensor cable length (per channel)
200 m
Operating temperature
–20…+85 ºC
AQ-02 point sensor
Light intensity threshold
8,000 lux
25,000 lux
50,000 lux
Pressure threshold (fixed)
0.2 bar above ambient pressure
Pressure measuring accuracy
±1.8 % (of full scale)
Detection radius
180º
A
AQ
Q-103L
-103LV
V
Instruction manual
Version: 1.00
39
© Arcteq Relays Ltd