Instruction manual – AQ 110 arc protection unit
16 (80
)
(CBFP) scheme may be enabled using the dipswitches. See Table 3-2 AQ 110
dipswitch SW 1 setting and Table 3-3: AQ 110 dipswitch SW 2 setting for details
of settings.
Figure 3-1 AQ 110 dipswitch SW1 and SW2
Dipswitch
Function selection
ON (LEFT
POSITION)
OFF (RIGHT
POSITION)
8
S1: L> / L>+I>
Sensor channel 1 trip
criteria
Trip on light only (L>).
Trip on light and
overcurrent (L> + I>).
Both signals are
required simultaneously
to trip.
7
S2: L> / L>+I>
Sensor channel 2 trip
criteria
Trip on light only (L>).
Trip on light and
overcurrent (L> + I>).
Both signals are
required simultaneously
to trip.
6
L> / L>+I>
Sensor channels 3-5
trip criteria (channel 3 in
AQ 110F)
Trip on light only (L>).
Trip on light and
overcurrent (L> + I>).
Both signals are
required simultaneously
to trip.
5
a/b
Selection of standard
arc scheme (SAS) type
SAS type a.
SAS type b.
4
Scheme select
Selection of standard
arc scheme (SAS)
Refer to chapter 6
Refer to chapter 6
3
Scheme select
Selection of standard
arc scheme (SAS)
Refer to chapter 6
Refer to chapter 6
2
Scheme select
Selection of standard
arc scheme (SAS)
Refer to chapter 6
Refer to chapter 6
1
Scheme select
Selection of standard
arc scheme (SAS)
Refer to chapter 6
Refer to chapter 6
Table 3-2 AQ 110 dipswitch SW 1 setting