Angle measurement inaccuracy
< ±1.0 degrees
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
4 mm
2
Burden (50/60 Hz)
<0.02 VA
Thermal withstand
300 V
RMS
(continuous)
9.1.1.3 Power and energy measurement
Table. 9.1.1.3 - 223. Power and energy measurement accuracy.
Power measurements (P, Q, S)
Frequency range
6…75 Hz
Inaccuracy
0.3 % <1.2 × I
N
or 3 VA of secondary
1.0 % >1.2 × I
N
or 3 VA of secondary
Energy measurement
Frequency range
6…75 Hz
Energy and power metering inaccuracy
0.5 S (50/60Hz) as standard
9.1.1.4 Frequency measurement
Table. 9.1.1.4 - 224. Frequency measurement accuracy.
Frequency measurement performance
Frequency measuring range
6…75 Hz fundamental, up to the 31
st
harmonic current or voltage
Inaccuracy
10 mHz
9.1.2 CPU & Power supply
9.1.2.1 Auxiliary voltage
Table. 9.1.2.1 - 225. Power supply model A
Rated values
Rated auxiliary voltage
85…265 V (AC/DC)
Power consumption
< 7 W
< 15 W
Maximum permitted interrupt time
< 60 ms with 110 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
332