Pick-up
P>
0.10…150 000.00 kW, setting step 0.01 kW
Prev>
-15 000.00…-1.00 kW, setting step 0.01 kW
P<
Low-power blocking P
SET
<
0.00…150 000.00 kW, setting step 0.01 kW
0.00…100 000.00 kW, setting step 0.01 kW
Inaccuracy:
- Active power
Typically <3.0 %P
SET
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (P
M
/P
SET
ratio 1.05
→
)
±1.0 % or ±35 ms
Instant operation time
Start time and instant operation time (trip):
- P
M
/P
SET
ratio 1.05
→
<50 ms
Reset
Reset ratio
97 or 103 %P
SET
Reset time setting
Inaccuracy: Reset time
0.000…150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
No
Notte!
e!
• Voltage measurement starts from 0.5 V and current measurement from 50 mA. In case either
or both are missing the power measurement is forced to 0 kW. If the settings allow it (low-
power blocking = 0 kW), the P< might be in the trip state during this condition. The trip is
released when the voltage and the current are begin to be measured.
• When the low-power blocking is set to zero, it is not in use. Also, all power measurements
below 1.00 kW are forced to zero ("P< blocked").
9.2.1.13 Non-directional undercurrent protection (I<; 37)
Table. 9.2.1.13 - 255. Technical data for the undercurrent function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
RMS phase currents
Pick-up
Pick-up current setting
0.10…40.00 × I
N
, setting step 0.10 × I
N
Inaccuracy:
- Current
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
Operation time
Definite time function operating time setting
0.00…150.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio 0.95)
±1.0 % or ±30 ms
Instant operation time
Start time and instant operation time (trip):
- I
M
/I
SET
ratio <0.95
<50 ms
Reset
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
348